APPENDIX H – SYSTEM GROUNDING
h-2
Hyspeed HT2000LHF
Instruction Manual
6
purchased locally, using a minimum 8 AWG UL Type MTW cable (USA specification) or the appropriate cable
specified by national and local codes.
Consult the appropriate manufacturer’s instructions to ground equipment that does not receive power from the
power supply.
Work Table Grounding
If a supplementary ground rod is installed near the worktable to reduce EMI, it must be connected directly to
the PE ground of the building structure, connected to the service ground; or to earth, providing the resistance
between the ground rod and the service ground meets national or local codes. Place the supplementary
ground rod within 20 ft (6 m) of the worktable according to national or local codes.
If any module is grounded to the work table, the work table must be grounded to the power supply, or the
configuration must be changed to comply with applicable national and local electrical codes.
A ferrite choke can be placed in the conductor between the work table ground rod and the PE ground, with a
number of turns through the choke to isolate the safety ground (at 60 Hz) from any electromagnetic
interference (frequencies above 150 Khz). The more turns the better. A suitable ferrite choke can be made by
wrapping 10 turns or more of the ground lead through Magnetics part number 77109-A7, Fair-Rite part
number 59-77011101, or other equivalent ferrite choke. Locate the choke as close as possible to the plasma
power supply.
Summary of Contents for HT2000LHF
Page 1: ...200 Volt Plasma Arc Cutting System Instruction Manual 803040 Revision 7 HySpeed HT2000LHF ...
Page 5: ......
Page 15: ...TABLE OF CONTENTS viii Hyspeed HT2000LHF Instruction Manual 6 ...
Page 109: ...MAINTENANCE 5 20 HySpeed HT2000LHF Instruction Manual 7 ...
Page 133: ......
Page 134: ...7 5 7 Figure 7 1 HT2000LHF Coolant Flow Diagram ...
Page 135: ......
Page 136: ...7 7 7 ...
Page 137: ......
Page 138: ...7 9 7 ...
Page 139: ......
Page 140: ...7 11 7 ...
Page 141: ......
Page 142: ...7 13 7 ...
Page 143: ......
Page 144: ...7 15 7 ...
Page 145: ......
Page 146: ...7 17 7 ...
Page 147: ......
Page 148: ...7 19 7 ...
Page 149: ......
Page 150: ...7 21 7 ...
Page 151: ......
Page 152: ...7 23 7 ...
Page 153: ......
Page 154: ...7 25 7 ...
Page 155: ......
Page 157: ......
Page 159: ......
Page 174: ...APPENDIX A ARGON HYDROGEN CUTTING AND GOUGING a 14 HySpeed HT2000LHF Instruction Manual 6 ...
Page 176: ...b 2 ...
Page 177: ...b 3 ...
Page 178: ...b 4 ...
Page 179: ...b 5 ...
Page 181: ...b 7 ...
Page 182: ...b 8 ...
Page 183: ...b 9 ...
Page 184: ...b 10 ...
Page 194: ...APPENDIX E AIR FILTERS e 2 Hyspeed HT2000LHF Instruction Manual 6 ...
Page 196: ...APPENDIX F AERATION MANIFOLD FOR CUTTING ALUMINUM f 2 Hyspeed HT2000LHF Instruction Manual 6 ...
Page 198: ...APPENDIX G IEC SYMBOLS g 2 Hyspeed HT2000LHF Instruction Manual 6 ...