Configuration
Serial Channel Source: This is the channel or physical interface that the device is attached, options are DBA, DBB and
SSI.
Authority Role:
This is the Modbus Authority, when set to Master the iRIS will interrogate the devices. When
set to Slave the iRIS responds to the master device requests.
Only one Slave device can be configured, all others are set to Master.
Slave Address:
This is the address of the Modbus slave, when the Authority Role is set to Master, this address
is for the device connected to the iRIS. When the Authority Roll is set to Slave, this address is
the Modbus address of the iRIS.
Start Offset:
Only Applies to Authority Roll Master: this offset the
Poll Interval
. For example, if the Poll
Interval is 15 seconds and the offset is 5, then the iRIS will poll the device every 15 seconds
offset by 5 seconds, 00:00:05, 00:00:20, 00:00:35, 00:00:50, 00:01:05, 00:01:20, 00:01:35 …
23:59:35, 23:59:50.
Poll Interval:
Only Applies to Authority Roll Master: this is the interval that the iRIS will make requests to the
given device.
Function Code:
Only Applies to Authority Roll Master: This is the Modbus Function code see section
for more details.
Write Register Value:
Only Applies to Authority Roll Master: This is a value that will be to the device if the function
code is set to 0x06 Write single register.
Endianness:
This is the Endianness of the data contained in the Modbus registers, see section
for more details.
Start
Register
number:
This is the Modbus registers start address, see section
for more details.
Registers List
62
62
62
Summary of Contents for iRIS Under Cover
Page 1: ...iRIS Under Cover User Manual ...
Page 13: ... 2022 HyQuest Solutions 13 Installation Figure 2 Mounting Diagram ...
Page 108: ... 2022 HyQuest Solutions 108 Appendices 8 1 Declaration of Conformity ...
Page 115: ... 2022 HyQuest Solutions 115 Appendices ...
Page 117: ...www hyquestsolutions com 2022 HyQuest Solutions 29 06 2022 ...