© 2022 HyQuest Solutions
94
Operation
Each segment always begins with a basic data header. At block with time series value(s) will follow the data header. After
each block the file can end or a further segment can follow. Empty lines and comments are ignored; they can stand in any
place in the file.
Figure 23 – ZRXP file block structure
Note
:
§
Comments begin with the character sequence “##” at the start of line.
§
Each line begins with a number sign (#).
§
The fields are separated by a separator (|*|)
The following is an example file contain data for two sensors, no samples for Rainfall (as it is event-based logging mode)
and 3 samples for the water level:
#ZRXPVERSION3014|*|ZRXPCREATORiRIS270|*|
#CDASANAMEInnovation Park|*|
#CDASAAG6-0006|*|
#TZUTC12:00|*|
#CNR01|*|
#CUNITmm|*|
#CNAMERainfall|*|
#REXCHANGEAG6-0006_01|*|
#RINVAL-777|*|
#LAYOUT(timestamp,value,primary_status)|*|
Data header
S
e
g
m
e
n
t
1
#ZRXPVERSION3014|*|ZRXPCREATORiRIS270|*|
#CDASANAMEInnovation Park|*|
#CDASAAG6-0006|*|
#TZUTC12:00|*|
Data header
S
e
g
m
e
n
t
2