96
MX3636-01 Rev. D
HydraSwing Programming & Operations
© 2018
Type
Alert/Fault/Error Display
Buzzer Chirp Sequence
Possible Cause & Suggested Corrective Action
FAULT
FAULT 5
LIMIT FAILED
2 chirps per second once per
minute
50VF series only.
Not applicable for StrongArm M30/
M50. Slow down to stop limit took too long. Possible
bad limit switch.
• Verify limits and placement of slow down limit ramps.
• With drive wheels clamped, test Open (GATE OPENING appears
on display). Test Close (GATE CLOSING appears on display.
FAULT
FAULT 14
STUCK GATE
2 chirps per second once per
minute
The STC has tried 3 times to overcome a stuck gate. The gate is
non-operational while this fault is triggered. Caused by broken gate
hardware or ice/snow buildup.
Check and correct gate hardware as required.
Press RESET to clear fault.
ERROR
ERROR 1
Direction Error
3 chirps per second once per
minute
Close Limit tripped after running Open or Open Limit tripped after
running Closed.
Assess cables and wire connections.
• Make sure wires are connected to the proper terminals. Make sure
gate handing (if applicable) is appropriate.
• Swap connections of hydraulic hoses, if necessary.
ERROR
ERROR 2
IES Disconnect
3 chirps per second once per
minute
• The IES sensor could be bad, check to see that the NC contact is
intact.
• Check that you have the most current sensor; visit our website
and
view the technical bulletins in the Tech Support area. The
sensor
wire could be loose; you may want to tighten the female
connectors with some pliers.
• Verify the version of the software by pressing the Reset button.
The software version appears on the display. Make a note of it. The
software version should be h4.50 or h5.50 (or later).
• If necessary, update the software using a PC laptop and S.T.A.R.T.
ERROR
ERROR 3
HY5 COMM ERROR
3 chirps per second once per
minute
One or more detectors are not communicating properly. Remove
detectors, reset the controller, and re-install detectors one at a time
until faulty detector or loop is found.
ERROR
ERROR 4
DUAL GATE
3 chirps per second once per
minute
Indicates a problem with the communication between the two gate
operators in a bi-parting (primary/secondary) gate system.
Check the software versions by pressing Reset or cycling power. The
version number flashes on the display (examples, h4.54 or h5.56).
The software versions on the Primary and Secondary gate should be
the same. If not, upload current software version using S.T.A.R.T. and
a PC laptop computer.
• Verify the Installer Menu item DG (DUAL GATE) is set to DG2 in
Primary and set to DG1 in Secondary gate operator.
• Make sure the wires are twisted and shielded. Refer to
• Be sure the low voltage wire runs, which include the bi-parting
gate communication wires, are separate from any high voltage
wires runs. Interference occurs if wire runs are mixed or too close
to each other.
The error automatically clears when the communication fault is
resolved.
ERROR
ERROR 6
DRIVE BOARD
3 chirps per second once per
minute
Internal error between the STC board and the VFD. Check cable
connections and wiring. Make sure both units are working properly.
ERROR
ERROR 7
MENU CHECKSUM
ERR7
3 chirps per second once per
minute
Contact HySecurity.
ERROR
ERROR 8
RPM SENSOR
3 chirps per second once per
minute
Check wiring from the hydraulic cylinder to the STC.
ERROR
ERROR 9
BATT DISCONNECT
3 chirps per second once per
minute
Only applies to DC Power Supply connection. Contact HySecurity.
Summary of Contents for HSG80F
Page 2: ...www SecureOpeners com 800 878 7829 Sales SecureOpeners com...
Page 14: ...Page intentionally left blank xiv MX3636 01 Rev D HydraSwing Programming Operations 2018...
Page 36: ...Page intentionally left blank 22 MX3636 01 Rev D HydraSwing Programming Operations 2018...
Page 124: ...110 MX3636 01 Rev D HydraSwing Programming Operations 2018 Page intentionally left blank...
Page 136: ...122 MX3636 01 Rev D HydraSwing Programming Operations 2018...