50
MX3636-01 Rev. D
HydraSwing Programming & Operations
© 2018
Installer Menu
Setting Options
Menu Tasks & Explanations
STC Wire
Connections
S3 0
SENSOR #3 TYPE
Same as Sensor 1
Same as Sensor 1
SENSOR 3
COM
+24V
SENSOR COM
PC 0 NO INPUT
PHOTO EYE
OUTPUT
0 = Normally Open NO input
1 = Normally Closed NC input
(monitored)
Changes occurring in 2016. See
NOTE
.
The default setting is for photo eyes with
Normally Close outputs. When set for NC,
the connection is monitored and any short
circuit fault will generate a FAULT 2 (
FAL2
)
alert. Press the Stop or Reset button to clear.
COM
+24V
COM
PHOTO EYE
CLOSE
DIRECTION
GC 0 NO INPUT
GATE EDGE
OUTPUT
0 = Normally Open NO input
1 = Normally Closed NC input
(monitored)
Changes occurring in 2016. See
NOTE
.
The default setting is edge sensor with
Normally Closed (NC) output. The optional
setting of 0 requires an (NO) output.
COM
+24V
COM
EDGE SENSOR
TC 1 (INTLOCK)
TIME CLK/INTLOCK
0 = TIME CLK (Select Time Clock)
1 = INTLOCK
(Select Open Interlock)
Configures the input at Terminal No. 7 on
the STC to be either for the gate interlock
function, or for an external time clock to
open input. The default setting is (TC_1) for
the interlock function.
INTERLOCK
OPEN (#7)
COM
DT 0 FREE EXIT
DISABLE FUNCTION
0 = Disable Free Exit
1 = Disable Close Timer
Configures Terminal #9 input to disable
either the Free Exit Detector function
or, alternately, the Close Timer function.
The default setting disables the free exit
detector.
NOTE:
When set to 0, the free exit
is disabled while the gate rests on it’s closed
limit. If the closed limit is not tripped, the
free exit continues to work normally.
DISABLE EXIT
DETECTOR (#9)
COM
OR 1 REVERSE
OUTSIDE OBS LOOP
0 = Pause closing only
1 = Enable reversing to open
2 = Ignore and continue closing*
The default (1) is for full reversal when the
Outside Obstruction Loop is triggered. A
setting of 0 causes the gate to only pause
when triggered. The gate closure begins as
soon as the loop is clear again. *A setting
of 2 is only available on CRASH barriers
and provides for the most secure facilities
where it is essential that the loop trigger
is completely ignored and the barrier arm
continues closing without pause or reversal.
OUTSIDE OBS
LOOP (#11)
COM or
connection to
Hy5B detector
IR 1 REVERSE
INSIDE OBS LOOP
0 = Pause closing only
1 = Enable reversing to open
2 = Ignore and continue closing*
The default is for full reversal when the Inside
Obstruction Loop is triggered. A setting
of 0 causes the gate to only pause when
triggered. Closure begins as soon as the
loop is clear again. *A setting of 2 is only
available on CRASH barriers and provides for
the most secure facilities where it is essential
that the loop trigger is completely ignored
and the gate continues closing without
pause or reversal.
INSIDE OBS
LOOP (#10)
COM or
connection to
Hy5B detector
NOTE:
The shaded Installer Menu items do not appear when Build Year is set to 2 (BY 2). Exceptions exist for barrier arms, CRASH
products, operators set to pre-2016 and Usage Class IV provisions.
Summary of Contents for HSG80F
Page 2: ...www SecureOpeners com 800 878 7829 Sales SecureOpeners com...
Page 14: ...Page intentionally left blank xiv MX3636 01 Rev D HydraSwing Programming Operations 2018...
Page 36: ...Page intentionally left blank 22 MX3636 01 Rev D HydraSwing Programming Operations 2018...
Page 124: ...110 MX3636 01 Rev D HydraSwing Programming Operations 2018 Page intentionally left blank...
Page 136: ...122 MX3636 01 Rev D HydraSwing Programming Operations 2018...