29
© 2012 Installation and Reference Manual D0125 Rev. H
Section 3
—Correctional Facility – User Optional Wiring
A special terminal strip has been pre-wired to the three user relay outputs in Correctional Facility (CF) models for easy
field wiring of the common interconnect options. If alternate output functions are required, see page 30.
NOTE: User 3 Relay on STC boards is rated for DC only up to 48V and does not have an N.C. (normally closed)
connection.
Connecting an Interlocked Pair:
An interlocked pair of operators is not a Master/Slave system. It is two gate operators interlocked such that the one cannot
open unless the other is fully closed. This connection is used frequently at correctional facilities for Sally Port gates. The
Smart Touch Controller provides both the required interlock input (#7) and the interlock output contact.
1. User relay 3 on the Smart Touch Board has been set by the factory to provide the necessary interlock function.
Connect a total of four wires between operator #1 and operator #2 as follows: One wire to the Common bus of
each operator to the User 3 relay COM terminal of the other operator. Then, connect wires from the User 3 relay
NO terminal to the Interlock input (#7) of the other operator.
2. If User relay 3 has already been used for a different function, then one of the other relays User 1 or User 2 must
be wired as described above and set to output function 1. The user relays are configured in the Installer Menu as
item [r1__], [r2__] or [r3__] according to the definitions described on page 30.
3. The interlock input, terminal #7, is convertible to alternately be a time clock input, so it is possible that it may need
to be switched back for the interlock function. If this alteration is needed, go to the Installer Menu, and set item
[tC _] to be [tC_1].
Connecting to an External Lock Mechanism:
The Smart Touch Controller can command an external solenoid lock or maglock to unlock just before gate motion begins.
1. User relay 2 has been set by the factory to provide the necessary output for a solenoid lock. Connect the voltage
matching the lock solenoid to User 2 COM and connect a solenoid coil to User 2 NO (connect a maglock coil to
User 2 NC). The un-switched solenoid or maglock wire connects directly to its supply voltage common conductor.
2. If User relay 2 has already been used for a different function, then one of the other relays User 1 or User 3 must
be wired as described above and set to output function 6. The user relays are configured in the Installer Menu as
item [r1__], [r2__] or [r3__] according to the definitions described on page 30.
Connecting the Gate Secure Position Indicator Output:
The Smart Touch Controller can signal an external device that the gate is secure.
1. User relay 1 has been set by the factory to provide the necessary output for position indication. Connect the
voltage matching the indicator light to User 1 COM and connect the gate secure light to User 1 NC. The other
indicator light wire connects directly to the voltage common conductor. If an unsecured light is required, connect it
to User 1 NO.
2. If User relay 1 has already been used for a different function, then one of the other relays, User 2 or User 3, must
be wired as described above and set to output function 1. The user relays are configured in the Installer Menu as
item [r1__], [r2__] or [r3__] according to the definitions described on page 30.
Summary of Contents for SlideDriver 50VF2
Page 2: ......
Page 28: ...14 2012 Installation and Reference Manual D0125 Rev H Section 2 Technical Drawings...
Page 29: ...15 2012 Installation and Reference Manual D0125 Rev H Section 2 Technical Drawings...
Page 36: ...22 2012 Installation and Reference Manual D0125 Rev H Section 3 Wiring Control Inputs...
Page 63: ...49 2012 Installation and Reference Manual D0125 Rev H Section 6 Internal Solenoid Lock Drawing...
Page 64: ...50 2012 Installation and Reference Manual D0125 Rev H Section 6 Internal Solenoid Lock Drawing...
Page 81: ...68 2012 Installation and Reference Manual D0125 Rev H...