30
© 2012 Installation and Reference Manual D0125 Rev. H
Section 3
—Options for User Programmable Output Relays 1-3
The Smart Touch Controller is able to interface with many types of external devices through the use of three user-
programmable output relays. All of the output functions described below are accessible in the Installer Menu under the
selection [r1__], [r2__] and [r3__].
NOTE:
The User Relays will operate normally to less than 18VDC.
Access the Installer Menu and program the output relays according to the following steps:
1. Select the relay you wish to use; either [r1__], [r2__] or [r3__].
2. Enter the appropriate function using the associated number listed in the table.
1.
Close limit output:
Creates an interlock signal to another operator’s interlock input, or simply to indicate that the gate
is secure. The relay is released when the fully-closed limit switch is tripped. The relay is energized when the fully-
closed limit is released.
2.
Close limit pulse output:
Used in a sequenced syst
em
to command a second machine to close. Generates a brief
pulsed output that occurs when the close limit is triggered.
3.
Open limit output:
Indicates a fully-opened position. This output becomes active when an open-limit is triggered and
releases when the open-limit is released.
4.
Open limit pulse output:
Trips a sequenced barrier arm gate operator to open. Generates a brief pulsed-output
when the open-limit is triggered. An additional pulse is also generated with any new open command even when the
gate is already fully-opened.
5.
Warn before/during operate output:
Controls an external warning device. This output operates at the same time as
the internal warn before operate buzzer.
6.
Gate Lock output:
Controls external solenoid locks or magnetic locks. In both directions of travel, this output is
activated about 7/10ths of a second before the operator starts moving the gate and remains active while moving as
well as for a few seconds after stopping.
7.
Gate forced open output:
Activated if the gate is forced off the closed limit switch and operator is not able to restore
the gate to full close within four seconds. This alarm resets itself in 30 seconds.
8.
Gate open too long output:
Activates when the gate is open longer than a user-selected period of time. Adjustable
from 0 delay to 135 seconds delay in 15-second time increments.
9.
Safety Mode Alert output:
Activated when system is in the Safety Mode or the Entrapment Mode. Safety Mode
occurs upon an impact with an obstruction. Entrapment Mode means the gate is stopped and occurs if the internal
inherent sensor triggers while the system is in the Safety Mode.
10.
Entrapment Mode Alert output:
Activated only when system is in the Entrapment Mode.
11.
Unauthorized Vehicle Entry output:
Activated when a second vehicle enters from the outside without a valid input
from an access control device. This output releases when an access control input signals open or the gate reaches
the close limit position.
12.
Outside Obstruction Vehicle Detector output:
Interlocks an entry device to prevent pedestrian use. This output is
active whenever the OOLD is tripped.
13.
Special output f
rom “OOLD” only when gate is closed:
Annunciates a vehicle or indicates loitering. Adjustable
from 0 delay to 135 seconds delay in 15-second time intervals.
14.
Gate nearing full travel output:
Applies to operators with RPM sensors only. Activated when the gate is three feet
from full travel in both the open and close directions. This output is used to reduce the sensitivity of a proximity
sensor near the ends of gate travel.
15.
Gate Failure output
: Activated to report occurrence of a problem. Indicates the system in an Error Mode, Fault Mode
or Entrapment Mode. If active, the gate is disabled.
16.
Motor Running output:
Active when the motor is running and the gate is in motion.
17.
AC Power Failure output:
This relay is normally energized and drops with loss of AC power. This output is also
active on DC machines when the battery charger is off.
18.
DC Power Failure output:
Activated when the battery power is very low, but the output ceases when the battery is
dead. The relay is triggered when the battery is less than 20 Volts.
Summary of Contents for SlideDriver 50VF2
Page 2: ......
Page 28: ...14 2012 Installation and Reference Manual D0125 Rev H Section 2 Technical Drawings...
Page 29: ...15 2012 Installation and Reference Manual D0125 Rev H Section 2 Technical Drawings...
Page 36: ...22 2012 Installation and Reference Manual D0125 Rev H Section 3 Wiring Control Inputs...
Page 63: ...49 2012 Installation and Reference Manual D0125 Rev H Section 6 Internal Solenoid Lock Drawing...
Page 64: ...50 2012 Installation and Reference Manual D0125 Rev H Section 6 Internal Solenoid Lock Drawing...
Page 81: ...68 2012 Installation and Reference Manual D0125 Rev H...