DISPLAY AND MENU OPTIONS
Table 11. Smart DC Controller - User Menu Functions
User Menu
Display
Setting Options
(Bold = Factory
Settings)
Menu Tasks and Explanations
Associated
DC Controller
Connections
CT 0 (OFF)
Close Timer
0 = Timer
disabled
1 second to 99
seconds
Assign how many seconds before open
gate initiates automatic closure. Keep
setting at 0 if a hard-wired, push-button
control device is being used.
NOTE:
CLOSE TIMER display does not
appear when HOLD TO CLOSE is set to 1.
Not applicable
(N/A)
HC 0 (OFF
Hold to Close
0 = off
1 = on
Set to 0 produces a gate closure when a
momentary signal is transmitted. Set to
1 if a constant hold to close signal, such
as a push button control, is being used.
A setting of 1 also deactivates automatic
close timer and causes its menu to
disappear. You must set HC to 1 to comply
with UL 325 Type D protection. Refer to
Table Notes.
COM
CLOSE
HO 0 (OFF)
Hold to Open
0 = off
1 = on
Similar to HOLD TO CLOSE, but configures
OPEN push button for a constant-hold
function.
0 = Momentary open signal
1 = Constant hold open push button
required. You must set HO to 1 to comply
with UL 325 Type D protection. Refer to
Table Notes
COM
OPEN
AP 0 AC LOSS
UPS FAIL OPEN
0 = UPS Fail
Open
1 = UPS Fail
Close
2 = Auto Open
3 = No Close
Timer
Setting designates what action gate
performs during an AC power loss. Refer
"Setting AC Power Loss Gate Function"
.
N/A.
RO 0 (OFF)
Radio Open/Close
0 = off
1 = on
Configures radio input for open only (0). If
changed to setting 1 then adds capability
for radio input to close gate, but only when
gate is fully open.
COM
RADIO OPEN
63
| www.hysecurity.com
SWINGSMART DC PROGRAMMING AND OPERATIONS MANUAL
MX3640-01 REV. D ©2018