BI-PARTING/DUAL GATE SYSTEM
Configuring two operators to be a Primary
and Secondary pair is easy with the Smart DC
Controller. There is no need to order a special
model or any adapters. The area of the board
marked Dual Gate employs a 3-wire RS-485 serial
port for communication between primary and
secondary operators. See Figure 54
.
POWER REQUIREMENTS
When installing a dual-operator system, the
following must be adhered to:
z
An electrical conduit for interconnecting wires
must span between the two operators. The dual
gate communication wires and any low voltage
control wires must be installed in a conduit that
is separate from the high voltage power wires.
See
.
z
Complete the installation of both operators as
separate machines and verify that their basic
functions are correct as solo operators before
interconnecting them.
z
External control inputs, vehicle detectors
and entrapment protection sensors may be
connected to either gate operator without
regard to preference.
z
Be sure both operators are running the same
software version. The software version is
available on the display by pressing the RESET
button on the operator. The software version
appears beneath the word HYSECURITY. Keep
the most current software loaded. It is available
at www.hysecurity.com. Make it part of your
maintenance routine to check for software
upgrades on a regular basis.
z
Both operators can be connected to the same
20A circuit breaker in the main panel. The wire
size affects operator performance. Use the
following chart as a guideline to size wire for
the given distance from the power source to
BOTH operators.
Table 16. Power Requirements
AC Power
14 gauge wire
12 gauge wire
10 gauge wire
Two operators 115V
305 ft (95 meters)
500 ft (150 meters)
775 ft (240 meters)
Two operators 230V
1220 ft (370 meters)
1950 ft (590 meters)
3100 ft (940 meters)
Figure 54. Primary-Secondary Pair
SENSOR
COM
+ 24 V
EMERG
OPEN
SHOW
LEDs
Connection for Primary/Secondary pair
USB Port
COM
DUAL GATE
RADIO OPTIONS
A
B COM OPEN +2
4V S1
COM NO
US
ER
2
DC ONLY
RS485
RS485
97