background image

Subject to change without notice.

Edition: 26 Feb. 2020      Ver. A0      Page 4/9

Intelligent Photocell (daylight detection prior to motion detection)

2

The built-in photocell will also automatically turn off the light when the ambient natural light exceeds the programmed lux level for 
more than 5min, regardless of whether motion is detected or not. This feature can be disabled if it is required that the fixture stays at 
dimmed level during absence.

With insufficient natural light, the sensor 
switches on the light automatically when 
presence is detected. 

With sufficient natural light, the light 
does not switch on when presence is 
detected.

The sensor switches off the light when 
natural light is sufficient, even with 
presence.

Note: if the stand-by time is preset at "+∞", the fixture never switches off but stays at preset dimming level even when natural light is sufficient.

zero-cross point

Alternating current

Zero-cross Relay Operation (HIM38/RF)

Designed in the software, sensor switches on/off the 
load right at the zero-cross point, to ensure that the 
in-rush current is minimised, enabling the maximum 
lifetime of the relay.

3

RF Grouping by Rotary Switch (Maximum 15 channels)

Noted: channel "0" is not for fast grouping, and sensors can only 
           be grouped by remote control.   

Transceiver  

Receiver

15 channels are available for fast grouping via rotary 
switch on both HIM38/RF and the receiver HC034RF. 
Simply selecting the same channel on each unit, the 
grouping is automatically completed.  

Typical Applications

For warehouse (HIM38/RF or HIM39/RF as both transmitter and receiver)

1

Settings on this demonstration:

Detection range: 100%    Hold-time: 10min   Daylight threshold: 100lux   Stand-by dimming level: 30%    Stand-by period: 10min   RX: STBY%   

Summary of Contents for HIM38/RF

Page 1: ...ve 1200W resistive max 20 devices max 40mA Capacitive Sensor RF Data Operation temperature Ta 20 O C 50 O C Environment IP65 IP rating Model No 0 2mW HF 5 8GHz 75MHz HF High Frequency microwave PIR Sensor principle Operation frequency Transmission power Detection range Detection angle RF frequency RF transmission distance Max O x H 18m x 15m 868MHz FSK mode default 30m indoor 50m outdoor 30s Warmi...

Page 2: ...ared remote receiver 1 10V 1 10V L N N L Installation hole 71 5 4 2 37 5 38 3 25 11 8 78 2 87 1 HC034RF 1 10V output RF grouping by rotary switch or remote control C Attach to the shade by clamp B Screw to the Luminaire by conduit Cable entry Sensor module PIR LED indicator Infrared receiver Rotary switch for programing Daylight sensor 59 6 66 6 89 9 0 825 75 64 43 8 43 59 3 73 5 35 2 57 3 47 5 Se...

Page 3: ...n is considered valid This is to prevent the sensor from false trigger by heat source air conditioner ventilation fans water pipe and elevators etc HF PIR either PIR or microwave mode to increase the detection capability and detection area 4 optional detection modes via remote control Sensor Sensor min 6m Distance Recommended between Sensors Pay attention The RF signal could be affected by big met...

Page 4: ...at the fixture never switches off but stays at preset dimming level even when natural light is sufficient zero cross point Alternating current Zero cross Relay Operation HIM38 RF Designed in the software sensor switches on off the load right at the zero cross point to ensure that the in rush current is minimised enabling the maximum lifetime of the relay 3 RF Grouping by Rotary Switch Maximum 15 c...

Page 5: ... Feb 2020 Ver A0 Page 5 9 Night Daytime HIM39 RF Brown LED driver L N DALI DALI L N Blue Red Black HIM38 RF Brown LED driver L N 1 10V 1 10V L N Blue Grey Red Black Wiring Diagram HC034RF LED Driver N N 1 10V N N L L L L _ 1 10V _ Wiring Diagram ...

Page 6: ...red for selection For single person walking across the detection range is reduced by 1 3 PIR detection H x D 15 x 18m max HF detection H x D 15 x 14m max PIR HF PIR tangential movement 18m HF walking across 14m 15m PIR detection L x W x H 18 x 5 x 15m max HF detection H x D 15 x 14m max PIR HF 15m 18m 14m 5m PIR HF PIR detection L x W x H 5 x 18 x 15m max HF detection H x D 15 x 14m max 15m 5m 14m...

Page 7: ...ight brightness during hold time Load Indication The light will flash ONCE rapidly after receiving the commamd from the remote control successfully Brightness Scene program 1 key commissioning Detection range for Transceiver only Press buttons in zone Detection range to set detection range at 100 75 50 10 Daylight threshold 1 Press button Start to program 2 Select the buttons in Detection range Da...

Page 8: ...e refer to steps below Short press Learn Erase button on RC to activate pairing mode and the receiver unit starts to beep once every second for 3min Note up to 30 units can be paired Short press Transmit button on RC the commander unit master unit beeps one time to send the transmission signal Upon receiving the transmission signal the receiver unit slave unit rapidly beeps 3 times in 1s to indica...

Page 9: ...Regarding precautions for PIR sensor installation and operation please kindly refer to www hytronik com download knowledge PIR Sensors Precautions for Product Installation and Operation 3 Regarding precautions for RF sensor installation and operation please kindly refer to www hytronik com download knowledge RF Sensors Precautions for Product Installation and Operation 4 Regarding Hytronik standar...