Fig. 3-3 Structure of cradle type / 그림 3-3 인출형 구조
12
<<
Vacuum Contactor Instruction Manual
3.4 Structure of Cradle Type and Interlock
1) Structure of cradle type
The Fig. 3-3 is the cradle type of HCA Series Vacuum
Contactor.
①
ON/OFF Indicator
ON means Closed condition, OFF means Open condition.
②
Counter
The Counter shows how many times the contactor
has operated since it was made.
The Counter may read 100 when you receive the
contactor, because it was tested in our factory or in
other place after manufacturing.
③
Trip Button
Only the latched types have the Trip Button which is
used in emergencies.
④
Control Plug
The control source is supplied through the Control Jack.
⑤
Position Interlock
The Position Interlock makes the contactor operate
only in the test and service position and prevents the
contactor from closing mechanically between TEST
and CONNECTION position.
⑥
Manual Closing Hole
Only latched types have a Manual Closing Hole which
is used to close the contactor manually.
3.4 인출형 구조 및 구속장치
1) 인출형 구조
인출형은 Fig. 3-3과 같이 구성되어 있습니다.
①
개폐 지시기
ON은 투입, OFF는 트립 상태를 나타냅니다.
②
계수기
ON/OFF 개폐횟수를 표시합니다. 제품 생산 후 성능 시험에 의하여
약 100회 정도로 개폐 되어 출고 됩니다.
③
트립 버튼
순시형에만 있는 긴급 트립용 버튼입니다.
④
컨트롤 플러그
21개의 pin이 있는 컨트롤 플러그를 통해 제어전원이 공급되고 보조
접점이 검출됩니다.
⑤
포지션 인터록
진공접촉기가 시험, 인입 위치에서만 ON/OFF 되도록 하는 기계적
인터록 장치입니다.
⑥
수동 투입구
순시형에만 있으며, 수동투입레버를 삽입하여 수동으로 투입시킵니다.
유지 보수시에 점검용으로만 사용됩니다.
⑦ ,⑩
⑧
⑨
③
④
⑤
②
①
⑥
①
ON/OFF Indicator
(개폐 지시기)
②
Counter (
계수기)
③
Trip Button (
트립 버튼)
④
Control Plug (
컨트롤 플러그)
⑤
Position Interlock (
포지션 인터록)
⑥
Manual Closing Hole (
수동 투입구)
⑦
Fuse (
퓨즈)
⑧
Fuse Melting Indicator (
퓨즈 용단 검출기)
⑨
Position Switch (
위치 검출 스위치)
⑩
Fuse Barrier (
퓨즈 베리어)
Structure and Explanation of Operation
구조와 작동원리
03