진공접촉기 취급설명서
>>
9
VC
|
HCA Series
2.4 Installation
1) Confirm the type and rating, make sure no damage
and clean contactors with dry cloths, before installing
contactors into the switchgear.
2) Mount contactors on a level floor referring to
guidelines for mounting dimensions in our catalogue
“HCA Series Vacuum Contactor”.
3) Clean the connecting surface with dry cloths, and then
connect main-circuit buses and earth terminals.
Be careful not to shock enclosures and contactors.
2.5 Inspection Before Operation
1) Confirm whether contactors are installed properly.
If not, install contactors each again according to clause 2.4.
2) Operate contactors a few times manually to ensure
that contactors closes and opens smoothly.
Then, operate contactors electrically in the test
position, and confirm that the ON/OFF indicator works
properly.
3) Confirm that no tools and materials are left near the
contactor.
2.4 설치 작업
1) 진공접촉기를 배전반에 설치하기 전 접촉기의 Type, 정격 및 손상여부
를 재확인하고, 마른걸레로 먼지 및 더러운 부분을 닦아냅니다.
2) 수평편차가 1 mm 이내가 되도록 설치되어야 하며, 설치 관련 치수는
“HCA Vacuum Contactor”Catalogue를 참조바랍니다.
3) 연결 부위를 깨끗이 닦아낸후 연결 및 접지 작업을 하여, 작업시 제품
에 무리한 힘이 걸리지 않도록 주의하십시오.
2.5 운전 전 점검사항
1) 결선이 정확한지 확인하고, 설치시 볼트 및 너트가 제대로 조여졌는지
확인하십시오.
2) 수동으로 개폐조작을 하여 동작의 이상유무와 ON/OFF 지시창의
동작을 확인하십시오.
시험위치에서 전기적으로 동작의 이상유무를 확인하십시오.
3) 진공접촉기 주위에 작업 공구가 남아 있는지를 확인하십시오.
�
Do not work on contactors unless the
primary circuit are disconnected by the
visible breaker.
�
When connecting bus-bars, tighten bolts
by the our standard.
�
Contactors are mounting on the
horizontal plane tightly.
�
설치에 앞서 모든 전원을 차단하기 위해 앞단의
차단기나 그러한 종류의 제품을 반드시 open
시켜 주십시오.
감전의 위험이 있습니다.
�
단자 bolt는 표준체결 torque로 확실하게 조여
주십시오. 화재의 위험이 있습니다.
�
본 제품은 수평하고 평평한 면에 단단하게 취부
하여 고정시켜 주십시오.