User manual
11
2.10
Electrical
Connection
Only
full
qualified
and
experienced
electrical
technicians
should
carry
out
electrical
installation,
service
and
repair
work.
Warning:
!
Make
electrical
connections
in
compliance
with
relevant
electrical
codes,
standards
or
other
requirements.
2.10.1
Cabling
Due
to
movement
of
generating
sets
on
their
vibration
mounts,
the
electrical
connection
to
the
set
should
be
made
with
flexible
cable.
The
cable
must
be
suitable
for
the
output
voltage
of
the
generating
set
and
the
rated
current
of
the
set.
In
determining
the
size,
allowances
should
be
made
for
ambient
temperature.
Method
of
installation,
proximity
of
other
cables,
etc.
All
connections
should
be
carefully
checked
for
integrity.
Current
carrying
capacity
of
power
cables
that
will
be
given
in
APPENDIX
A.
On
the
other
hand,
there
is
a
one
more
important
point
while
cable
cross
sections
are
being
selected.
If
the
distance
between
load
and
generator
is
too
length,
voltage
falling
at
the
load
side
can
be
too
much
at
the
transient
current
duration.
The
voltage
drop
across
a
cable
can
be
determined
as
follows:
1000
)
Xsin
Rcos
I
L
3
Δ
U
Δ
U
Voltage
drop
(V)
L
Length
of
conductors
(m)
I
Rated
current
(A)
R
Resistance
(
Ω
/km
to
VDE
0102)
X
Reactance
(
Ω
/km
to
VDE
0102)
Refer
to
APPENDIX
E
Cable
Current
load
standard.
2.10.2
Grounding
/
Earthing
Requirements
The
frame
of
the
generating
set
must
be
connected
to
an
earth
ground.
Since
the
set
is
mounted
on
vibration
isolators,
the
ground
connection
must
be
flexible
to
avoid
possible
breakage
due
to
vibration.
Ground
connection
cables
or
straps
should
have
at
least
full
load
current
carrying
capacity
and
meet
applicable
regulations.
2.10.3
Insulation
Test
Before
starting
the
generating
set
after
installation,
test
the
insulation
resistance
of
the
windings.
The
Automatic
Voltage
Regulator
(AVR)
should
be
disconnected
and
the
rotating
diodes
either
shorted
out
with
temporary
links
or
disconnected.
Any
control
wiring
must
also
be
disconnected.
A
500
V
Megger
or
similar
instrument
should
be
used.
Disconnect
any
earthing
conductor
connected
between
neutral
and
earth
and
megger
an
output
terminal
to
earth.
The
insulation
resistance
should
be
in
excess
of
1M
Ω
to
earth.
Should
the
insulation
resistance
be
less
than
1M
Ω
winding
must
be
dried
out.
2.11
Power
distribution
system
Our
diesel
engine
generator
set
use
three
phase
five
line
system
for
power
distribution.
That
is,
three
phase
live
wires,
one
neutral
line,
one
ground
line.
The
neutral
line
and
the
ground
line
are
not
connected.
Users
can
choose
three
phase
four
lines
for
power
distribution
according
to
requirement
that
is
to
connect
the
neutral
line
to
the
ground
(base
frame),
so
that
to
solve
the
problem
of
feint
that
the
neutral
line
sometimes
is
electriferous.
Note:
HYUNDAI
Power
series
diesel
engine
generator
sets
require
users
to
safely
connect
generator
sets
and
base
frames
to
the
ground,
please
refer
to
the
ground
label
for
connecting
point.
Summary of Contents for DHY22KSEm
Page 2: ...DIESEL GENERATOR Models Hyundai Engine Series Operation and Maintenance manual ...
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ...APPENDIX E 1 ...
Page 40: ...2 ...
Page 41: ...3 ...
Page 44: ...APPENDIX H ...
Page 45: ......