User manual
18
4
Maintenance
4.1
General
outline
For
different
types
of
generator
sets,
users
need
to
refer
to
the
matched
engine’s
operation
and
maintenance
manual
to
implement
correct
maintenance
operation.
In
order
to
obtain
maximum
operation
safety
and
life
expectancy
of
the
generator
sets,
periodic
maintenance
is
very
important.
Strictly
observance
of
the
terms
on
generator
set’s
maintenance
can
ensure
generator
set’s
performance
and
reduce
its
damage
to
environment.
Correctly
identify
and
strictly
observe
the
labels
(drawings,
words
and
warnings
etc.)
On
diesel
generator
sets
can
be
of
great
help
to
correct
maintenance
and
safe
operations.
Maintenance
of
the
generator
sets
shall
be
made
when
it
has
been
stopped
and
the
cable
which
connect
to
the
negative
polar
of
the
battery
shall
be
dis
‐
connected
so
that
to
ensure
the
generator
set
will
not
mistakenly
start.
4.2
Engine
Each
time
before
start
the
engine
!
Check
lubricant
oil
level
!
Check
coolant
level
!
Check
air
filter
indicator
!
Check
the
ventilation
of
radiator
and
ambient
environment
!
Check
engine’s
transmission
belt
!
Check
fuel
supply
status
Generator
sets
which
run
frequently
need
to
be
checked
one
time
every
6
to
8
hours.
Backup
generator
sets
need
to
be
checked
once
more
after
being
stopped.
Depends
on
the
new
generator
set’s
running
status,
when
it
is
necessary,
within
100
to
300
Hours,
following
actions
shall
be
taken:
!
Check
the
valve
clearance
!
Check
the
fuel
injector
For
each
0~50
hours
of
running
!
Discharge
the
water
remained
in
the
oil
‐
water
separator
!
Check
the
battery’s
electrolyte
level
(except
maintenance
free
battery)
For
each
50~600
hours
of
running
or
at
least
each
12
months
!
Change
lubricant
and
lubricant
filter
!
Because
the
quality
of
lubricant
oil,
sulfur
content
of
the
fuel,
and
lubricant
consumption
rate
of
each
engine
is
different,
the
interval
for
lubricant
oil
change
for
each
generator
set
will
be
different.
When
change
the
lubricant
oil,
at
the
same
time
oil
filter
needs
to
be
changed,
otherwise
the
change
of
oil
will
become
meaningless.
On
the
contrary,
if
the
lubricant
oil
remains
in
good
status,
we
can
filter
the
lubricant
much
better
by
change
the
oil
filter.
!
Change
fuel
filter,
clean
or
change
first
stage
fuel
filter
core,
oil
water
separator’s
core
(some
of
the
generator
sets
have),
check
and
organize
fuel
pipes
arrangement.
!
The
change
interval
of
above
fuel
filter
(core)
depends
on
the
quality
of
fuel
(if
it
contains
many
impurity),
the
fuel
adding
method
is
reasonable
or
not,
the
fuel
tank
is
cleaned
periodically
or
not
(contaminant
discharge).
Once
the
color
of
engine
exhaust
air
is
found
to
be
abnormal
and
the
output
power
decrease,
first
the
fuel
system
needs
to
be
checked.
For
each
400
hours
of
running
!
Check
and
adjust
the
transmission
belt
and
change
it
when
necessary
!
Check
and
clean
radiator
core
!
Discharge
deposit
in
the
fuel
tank
For
each
800
hours
of
running
!
Check
if
the
turbocharger
has
leakage
!
Check
if
the
air
inlet
pipes
has
leakage
For
each
1200
hours
of
running
!
Adjust
valve
clearance
For
each
2000
hours
of
running
or
at
least
24
months
!
Change
air
filter
(depend
on
ambient
air
quality,
decide
if
this
need
to
be
changed
earlier)
!
Change
coolant
and
coolant
filter
(some
generator
sets
have)
!
Thoroughly
clean
radiator
core
and
water
path
For
each
2400
hours
of
running
!
Check
fuel
injector
!
Thoroughly
check
and
clean
turbo
‐
charger
!
Comprehensively
check
engine
equipment
Summary of Contents for DHY34KSE
Page 2: ...DIESEL GENERATOR Models Hyundai Engine Series Operation and Maintenance manual ...
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ...APPENDIX E 1 ...
Page 40: ...2 ...
Page 41: ...3 ...
Page 44: ...APPENDIX H ...
Page 45: ......