Fig.5.7 Cooling Operation Flow Diagram (START)
Fig.5.8 Cooling Operation Flow Diagram (STOP)
5.5 Heating Operation
5.5.1 Start-up
(1) Operate the hot water pump.
When the flow rate reaches about 80% of the setting rate, the indication lamp,
“CHILLED/HOT WATER FLOW RATE” goes off.
Air purge
Igniting system operation
Flame detection
Solution pump Operation
Main fuel valve open
Over specified temp.
of H.P. gen.
Refrigerant pump operation
Igniting system Stop
Temperature control start
Main stop switch ON
Dilute operation
(Approx. 20 min.)
Damper low
Combustion position
Solution pump stop
Below prescribed
Temp. of H.P. gen.
Main fuel valve close
Forced fan stop
Refrigerant pump stop
Start switch ON
Chilled water thermostat ON
(with cooling load)
Chilled water flow rate .
Cooling water pump operation.
H.P. gen. Solution level.
H.P. gen. Temperature
Exchange gas temperature
Gas pressure (Applied for gas fired
type)
Chilled water temperature
Normal
Forced fan motor ON
Normal air pressure