background image

PAGE 16 

Rev 2 

 

5.10

 

Tandem compressors with timed control unit. (fig. 17). 

5.10.1

 

.1 Fit the plug in the power socket (fig. 13) and turn the pressure switch to 

position “I” (ON). Turn the master power switch “A” on the control unit to position I – 

power On is signalled by white indicator-light “E” going on. 

5.10.2

 

.2 Turn switch “B” to start the compressor. 

5.10.2.1

 

.1 Pos. 1 pumping element n. 1 only is operating 

5.10.2.2

 

.2 Pos. 2 pumping element n. 2 only is operating 

5.10.2.3

 

.3 Pos. 3 both pumping elements are operating simultaneously, 

at staggered starting times. 

5.10.3

 

.3 The compressor is fully automatic, and is controlled by the pressure switch 

which stops it when tank pressure reaches maximum value and restarts it when it falls 

to  minimum value. 

 

 

The head/cylinder/delivery tube unit can reach high temperatures. Take care when working near 

these parts, and do not touch them to avoid possible burns (fig. 18 - 19). 

 

IMPORTANT 

The electro-compressors must be connected to a power socket protected by a suitable differential 

switch (thermal-breaker). The motor of GM-TR compressors is equipped with an automatic 

thermal breaker located inside the winding – this stops the compressor when motor temperature 

reaches excessively high values. 

If the breaker is tripped, the compressors restarts automatically after 10 to 15 minutes. The 

motors of compressor models VX are supplied with a manually resetting automatic amperometric 

thermal-breaker, located outside the terminal board cover. 

When the breaker is tripped, wait for a few minutes and then reset the breaker manually (fig. 20). 

The motors of the AB series compressors are supplied with a manually resetting amperometric 

thermal-breaker, located on the terminal board cover. When the breaker is tripped, wait for a few 

minutes and then reset the breaker manually (fig. 20). 

The safety davice is automatic in three-phase and silent compressors. When the thermal-breaker is 

tripped, the pressure switch is released to “0” (OFF) position. 

Wait for a few minutes and return the pressure switch to “I” (ON) position (with the exception of 

models: AB 100/245-335 Three-phase - AB 150/ 245-335 Three-phase - AB 200/245-335 Three- 

phase). For compressors supplied with a control unit, the thermal-breaker is installed inside the 

control unit. When the thermal-breaker is tripped, observe the following procedure (fig. 22): 

 

Turn the switches on the control unit cover to position “0”, open the cover and press push- 

button 1 of the thermal-breaker. Close the cover of the control unit and restart the compressor, 

observing the operations described in the paragraph “Starting compressors with control unit”. 

The same instructions apply to compressors powered at 60 Hz.

 

 

5.11

 

Adjusting the operating pressure (fig. 23). 

5.11.1

 

.1 You do not have to use the maximum operating pressure at all times. On the 

contrary, the pneumatic tool being used often requires less pressure. On compressors 

supplied with a pressure reducer, operating pressure must be correctly adjusted. 

5.11.2

 

.2 Release the pressure reducer knob by pulling it up, adjust pressure to the 

required value by turning the knob clockwise to increase pressure and anti-clockwise to 

reduce it. 

5.11.3

 

.3 When you have obtained optimum pressure, lock the knob by pressing it 

downward (fig. 23). For pressure reducers equipped without a pressure gauge, the set 

pressure can be seen on the graduated scale located on the reducer body. 

Summary of Contents for HY30100

Page 1: ...ELECTRIC AIR COMPRESSOR Models HY3050 HY30100 HY3150 User Manual...

Page 2: ...3 4 2 UNPACKING USGAE INSTRUCTIONS 5 8 3 PART LOCATIONS 8 4 SPECIFIC SAFETY 9 11 5 OPERATION MAINTENANCE TROUBLESHOOTING 12 19 6 SPECIFICATION 20 7 WIRING DIAGRAM 20 8 GENPOWER CONTACT DETAILS 21 9 D...

Page 3: ...tock and property 1 2 Some or all of the following PPE Warning Signs and symbols may appear throughout this manual and you must adhere to their warning s Failure to do so may result in personal injury...

Page 4: ...l electrical cables plugs and connections for the following 1 3 3 1 Are intact and have no signs of damage to include but not limited to bare wires chaffing cuts and loose wiring If there are any sign...

Page 5: ...2 UNPACKING USAGE INSTRUCTION PAGE 5 Rev 2...

Page 6: ...PAGE 6 Rev 2...

Page 7: ...P AGE7 Rev 2...

Page 8: ...OMPRESSED AIR OUTLET 2 TANK 3 PRESSURE REDUCER 4 BELT GUARD 5 COMRESSOR UNIT 6 ELECTRIC MOTOR 7 PRESSURE SWITCH 8 PRESSURE GUAGE 9 PIVOT WHEEL 10 CONDENSATE DRAIN 11 WHEEL 12 CHECK VALVE PAGE 8 Rev 2...

Page 9: ...r working order If maintenance or servicing requires the removal of a guard or safety features be sure to replace the guards or safety feature before resuming operation of the compressor 4 3 Always we...

Page 10: ...clean The motor air vent must be kept clean so that air can freely flow at all times Check for dust build up frequently 4 19 Always operate compressor at its rated voltage Operate the compressor at vo...

Page 11: ...ding earthing wire 4 31 4 Never connect the green and yellow wire to a live terminal 4 32 Extension leads 4 32 1 Use only three extension leads that have three pin grounding earthing type plugs and th...

Page 12: ...ll securing it in a suitable way 5 1 6 To allow for good ventilation and efficient cooling the compressor s belt guard must be at least 100 cm from any wall fig 4 5 1 7 Compressors fitted on the tank...

Page 13: ...rection of the arrow on the belt guard or on the protective housing In the SILENT compressor check if the air flows is in the direction illustrated in fig 21A 5 2 3 Turn or press into position 0 accor...

Page 14: ...compressors are supplied with a manually resetting amperometric thermal breaker located on the terminal board cover When the breaker is tripped wait for a few minutes and then reset the breaker manual...

Page 15: ...es compressors are supplied with a manually resetting amperometric thermal breaker located on the terminal board cover When the breaker is tripped wait for a few minutes and then reset the breaker man...

Page 16: ...ries compressors are supplied with a manually resetting amperometric thermal breaker located on the terminal board cover When the breaker is tripped wait for a few minutes and then reset the breaker m...

Page 17: ...in the tank must be drained at least once a week by opening the drain tap fig 26 under the tank 5 12 5 Take care if there is compressed air inside the cylinder and water could flow out with considerab...

Page 18: ...NUOVA STILMOIL Arrow5W50 400 Other types of oil mineral multigrade SAE15 W40 100 5 14 Troubleshooting IMPORTANT DO NOT on any account unscrew any connection while the tank is pressurised Always check...

Page 19: ...a top above floor height it must be secured to prevent it falling while in operation DO NOT put objects or your hands inside the protective grilles to avoid injury to yourself or damaging the compres...

Page 20: ...150 100 Free air delivery CFM L min 9 255 9 255 9 255 Displacement CFM L min 13 368 13 368 13 368 Air Outlet Valve Tap Valve Tap Valve Tap Output pressureregulationtype Fixed Fixed Fixed Drivetype Bel...

Page 21: ...0 1646 686198 8 3 Email contact Techinical service genpower co uk 8 4 Web site www hyundaipowerequipment co uk 9 DECLARATIONS of CONFORMITY 9 1 Genpower Ltd confirms that this Hyundai product conform...

Page 22: ...and old electrical and electronic equipment separately 10 1 Disposing of packaging 10 1 1 The packaging consists of cardboard and correspondingly marked plastics that can be recycled 10 1 2 Recycle al...

Page 23: ...PAGE 23 Rev 2...

Page 24: ...www hyundaipowerequipment co uk Isaac Way London Road Pembroke Dock UNITED KINGDOM SA72 4RW T 44 0 1646 687 880 F 44 0 1646 686 198 E info hyundaipowerequipment co uk...

Reviews: