COBALT Pro
™
Wall Sensor Activated
Exposed Flush Valve Installation Instructions
I-CON Systems, Inc., for product support call 1-866-730-7192 or visit us online at support.i-con.com
One or more products contained herein are protected by U.S. Patent with other undergoing the patent process www.i-con.com/patents
Part No. 101822 : 3000 Series
Step 2
Connect cables for pressure and temperature sensor, control
module, solenoid, and power.
Step 3
Plug-in transformer. Power on interface module using external
power switch. Close interface module.
ADJUSTING CONTROL STOP
Step 1
Turn adjustment screw
COUNTERCLOCKWISE
1/2 turn from
closed position. Activate flush valve.
page 10
Rev 080323
Step 2
To adjust flush valve, turn adjustment screw in small increments.
Activate flush valve after each adjustment. The proper flow rate
should completely cleanse fixture without splashing water
outside of fixture.
NOTE:
The flow from the valve must never exceed the flow
capacity of the fixture. If a valve failure should occur, the fixture
must be able to accommodate a continuous flow from the valve.
Step 3
Reinstall control stop cap.