DANGER
THE FOLLOWING APPLIES ONLY TO QUALIFIED PERSONNEL:
Hazard of electrical shock, fi re or explosion. All installation, servicing and testing
referred to in this manual must be performed by qualifi ed personnel. All power should
be disconnected prior to removing covers or enclosures and where live conductors
may otherwise be exposed.
Failure to observe these precautions will result in death or severe personal injury.
The MGFR is designed with solid state electronics to ensure long-term trouble-free operation. Since a relay is
an intermediate device between a current sensor and a circuit breaker, any malfunction of the breaker during a
fault may not necessarily be attributed to the relay. If any abnormal behaviour is noted, it is better to perform the
SELF TEST operation, including breaker trip operation. This will help to determine which of the three devices is
responsible for the problem. The following sections outline some problems and their
probable causes, and suggest appropriate corrective action.
7.2.1 FAILURE TO TRIP
Failure of the circuit breaker to trip in response to a fault may be caused by any of the reasons below:
a) Relay set too high - Check that the pick-up settings on the relay are correct.
b) Supply not grounded or neutral grounded on the downstream side of the main sensor.
c) ZSCT improperly connected - Check that all connections are tight, wiring is correct and leads are not
broken. Any current sensor with an open circuited secondary must be replaced.
d) Failure to trip on SELF TEST on -SE Types may result when the TEST current is not present, because of
TEST winding connections, or control supply is not adequate (Should be 120V, 250 VA minimum). The self-
test winding is only available on I-Gard type RZ sensors, therefore if any other types are used, the self-test
will not work.
e) Shunt-trip solenoid open circuited - Check that the wiring of the trip solenoid is not broken.
7.2.2 FAILURE TO CLOSE BREAKER
DANGER
Personnel Safety Hazard
It is not advisable to turn off the relay power supply and close the breaker under
this situation. If a fault already exists in the system, this kind of operation may cause
personal injury and/or damage to the equipment connected to the system.
Failure to observe these precautions may result in death or severe personal injury.
7.2 TROUBLESHOOTING
Summary of Contents for MGFR Series
Page 1: ...C 322EM Instruction Manual March 2015 GROUND FAULT RELAY GROUND FAULT RELAY MGFR ...
Page 17: ...FIGURE 1 BLOCK DIAGRAM OF MGFR RELAYS ...
Page 21: ...FIGURE 5 CONNECTION DIAGRAM FOR MGFR RELAYS ...
Page 22: ...FIGURE 6 CONNECTION DIAGRAM FOR MGFR SE ZB RELAYS ...
Page 24: ...www i gard com Phone 905 673 1553 Toll Free 1 888 737 4787 Fax 905 673 8472 sales i gard com ...