background image

10

The auxiliary fault relays operate exclusively in the shunt (non-failsafe) mode. When the SIGMA-MD monitor relay is 
operating and no fault condition is present, the auxiliary fault relays are idle or de-energized. If a fault condition is 
detected and qualified, the appropriate auxiliary fault relay is tripped or energized.

The SIGMA-MD monitor relay uses non-volatile memory to store the states of the trip and auxiliary fault relays in 
case of a loss of control power.

If the trip memory option is ON and the SIGMA-MD monitor relay is powered down while indicating a fault condition, 
the trip, NGR and GND auxiliary fault relays are restored to the states these relays were in at the time of the power 
loss when control power is restored. If an NGR Fault was indicated at the time of the loss of control power, the NGR 
fault relay will be restored to a tripped state when control power is restored. Similarly, if a GND fault was indicated 
at the time of the loss of control power, the GND fault relay will be restored to a tripped state when control power is 
restored. The main trip relay will be set to a trip state if either of the NGR or GND auxiliary fault relays is restored to a 
trip state.

If the trip memory option is ON and, when control power is restored, if the NGR or GND fault relays are restored to a 
trip state, the LED associated with the fault relay, i.e. NGR Fault or GND fault is set flashing. The trip relay, auxiliary 
fault relays and associated LED will remain as such indefinitely regardless of whether a fault is present on the 
system and until the conditions which caused the trip are cleared and the relay is manually reset.

When SIGMA-MD monitor relay is manually reset, the states of the trip relay and auxiliary fault relays are set to their 
respective idle states in the relay’s operating memory and are then stored in the non-volatile memory.

6. LED INDICATORS AND DIAGNOSTICS

The SIGMA-MD monitor relay has four light emitting diodes (LEDs) located on its front panel. These LEDs are the 
Green PWR (Power) LED; the Red GND (Ground) FAULT and NGR FAULT LEDs; and the ZONE GR (Zone Grading) LED.

6.1 START-UP AND RESET INDICATIONS

The SIGMA-MD monitor relayhas a start-up sequence where the Red GND FAULT, NGR FAULT and ZONE GR. LEDS 
flash ON and OFF twice before being turned OFF. The Green PWR (Power) LED may also flash before it is turned ON. 
These indications will be the same whether the start up is a result of a manual reset or the application of control power.

During a manual reset the Red GND FAULT, NGR FAULT and ZONE GR. LEDs are turned ON for two seconds as an 
indication that a reset sequence is taking place. During this time the Green PWR (Power) LED will be FLASHING. 
After these indications the SIGMA-MD monitor relay resets giving the start-up indications described above.

After the SIGMA-MD monitor relay has gone through the start-up sequence and is operating normally the Green 
PWR (Power) LED will be ON and the Red GND, FAULT, NGR FAULT and ZONE GR LEDS will be OFF.

Summary of Contents for SIGMA-MD

Page 1: ...C EG42EM Instruction Manual December 2018 Previously C 455EM GROUND FAULT RELAY NEUTRAL GROUNDING RESISTOR SIGMA MD...

Page 2: ...s 10 6 1 Start Up and Reset Indications 10 6 2 Power on Led Green 11 6 3 Ground Fault Led Red 11 6 4 NGR Fault Led Red 11 6 5 Zone Ground Led Red 12 7 Self Test 12 8 Relay Settings 13 8 1 Trip Relay O...

Page 3: ...omer service and technical leadership We build on this foundation by investing in developing new products in electrical safety education including EFC scholarship program by actively participating in...

Page 4: ...present Hazard of Electrical Shock Burn or Explosion All installation servicing and testing referred to in this manual must be performed by qualified personnel All power should be disconnected prior...

Page 5: ...minal value When the ZSCS current is below 1 of the NGR let through current setting the SIGMA MD monitor relay simply monitors the NGR resistance for continuity i e whether the NGR is open or presents...

Page 6: ...fast response is necessary as failure of the NGR implies that there is limited ground fault protection on the system It also ensures fast tripping when a transformer is energized and the resistor is...

Page 7: ...necting the NGRS from the SIGMA MD monitor relay the R terminal of the NGRS should be disconnected BEFORE the Ground connection is removed from the G terminal of the SIGMA MD monitor relay The procedu...

Page 8: ...e trip relay terminals the auxiliary fault relay terminals the external reset test and the G F meter terminals If door panel mounted or remote test and or reset controls are required connect momentary...

Page 9: ...MD MONITOR RELAY AND NGR The SIGMA MD monitor relay has settings for the let through current ground fault trip current level and ground fault time delay These settings may be specified in the installa...

Page 10: ...r if the SIGMA MD processor fails this normally closed relay will open The contacts will close when the power LED turns on and remain closed as long as the relay is operating correctly All relays are...

Page 11: ...et flashing The trip relay auxiliary fault relays and associated LED will remain as such indefinitely regardless of whether a fault is present on the system and until the conditions which caused the t...

Page 12: ...l be ON when the SIGMA MD monitor relay has detected and qualified a ground fault The RED GND FAULT LED will remain ON until the SIGMA MD monitor relay is manually reset even if the NGR fault conditio...

Page 13: ...GMA MD monitor relay and no voltage applied to system transformer s primary winding Alternatively the system transformer s primary winding may be powered with the system transformer secondary isolated...

Page 14: ...en control voltage is applied to the SIGMA MD monitor relay and the system is operating normally The trip relay is energized trip when the measured values of the ground fault current or NGR resistance...

Page 15: ...A MD monitor relay will resume monitoring of the system and if a fault remains on the system will detect the fault and will re trip de energizing the trip relay 8 2 TRIP MEMORY SETTING The SIGMA MD mo...

Page 16: ...ble and not higher than 20 when complying with this CSA Mine Safety Standard 8 5 SYSTEM FREQUENCY The SIGMA MD monitor relay has two settings for selecting the AC frequency of the system it monitoring...

Page 17: ...is Idle Not Tripped Trip Relay is not energized Aux Fault Relays are not energized DOWN SIGMA MD Relay is Tripped Trip Relay is energized Aux Fault Relays are energized MODE DIP SWITCH SETTING Table 1...

Page 18: ...U U D 1550 D U U U U 1650 U D D D D 1750 U D D D U 1850 U D D U D 1950 U D D U U 2050 U D U D D 2150 U D U D U 2250 U D U U D 2350 U D U U U 2450 U U D D D 2550 U U D D U 2650 U U D U D 2750 U U D U U...

Page 19: ...y U UP D DOWN Table 4 Ground Fault Trip Current Level Settings SYSTEM FREQUENCY 60 50 Hz DIP SWITCH SETTING SYSTEM FREQUENCY 50 Hz UP SYSTEM FREQUENCY 60 Hz DOWN DIP switch 11 right hand array U UP D...

Page 20: ...CS 550 U D U D I GARD TxA Type ZSCS 600 U D U U I GARD TxA Type ZSCS 650 U U D D I GARD TxA Type ZSCS 700 U U D U I GARD TxA Type ZSCS 750 U U U D I GARD TxA Type ZSCS 800 U U U U I GARD TxA Type ZSCS...

Page 21: ...restored after a loss of control power the trip relay and auxiliary fault relays are returned to the state these relays had prior to the loss of control power The state of the trip relay and auxiliary...

Page 22: ...s open or presents some resistance Trip Time Less than 60 seconds per CAN CSA M421 00 Typically 3 5 seconds 0 100 msec Up to 10 seconds under certain conditions Accuracy NGR Trip Resistance limits in...

Page 23: ...the conductor on terminal G of the NGRS XX resistor sensor from ground and ensure the conductor is insulated 4 Disconnected the conductors between the X1 and X2 terminals of the TxA type ZSCS and the...

Page 24: ...in less than 1s if ground fault current exceeds 20 of the prospective ground fault current 3 6 2 Neutral Grounding Devices A neutral grounding device shall be a continuously rated except when ground f...

Page 25: ...24 Figure 2 Sigma MD Monitor Relay Detail A Typical NGRS Sensing Resistor Ngrs 6 Dual Voltage Model Shown Figure 3 Low Voltage NGRS Resistor Sensor...

Page 26: ...25 Figure 5 NGRS 50 Figure 4 NGRS 25...

Page 27: ...26 Figure 6 High Voltage NGRS Resistor Sensors...

Page 28: ...www i gard com Phone 905 673 1553 Toll Free 1 888 737 4787 Fax 905 673 8472 support i gard com...

Reviews: