background image

22

11. CATALOGUE NUMBERS

SIGMA-MD MONITOR RELAY 

 

 

Ground Fault Relay & Neutral Grounding Resistor Monitor

      (Special 

Order: 

SIGMA-MD)

GFU-AM1 

 

 

 

 

Analog Meter, 3 ½ in. 0-1 mA with Scale 0-100%

NGRS-XX RESISTOR SENSOR   

 

Resistor Sensor

T2A ZERO SEQUENCE CURRENT SENSOR 

With a 2 inch (5.08 cm) window.

T3A ZERO SEQUENCE CURRENT SENSOR 

With a 3 inch (7.62 cm) window. 

T6A ZERO SEQUENCE CURRENT SENSOR 

With a 6 inch (15.24 cm) window. 

T9A ZERO SEQUENCE CURRENT SENSOR 

With a 9 inch (22.86 cm) window.

APPENDIX A

High-pot and dielectric testing of the system.

As the SIGMA-MD monitor relay, NGRS-XX resistor sensor and TxA type zero sequence current sensor have 
undergone and passed high-pot testing at the factory, field testing of the relay is unnecessary and may damage 
these components. For any high-pot tests or dielectric withstand tests on the system conducted in the field, the 
SIGMA-MD monitor relay, NGRS-XX resistor sensor and TxA type ZSCS must be prepared as described below to 
avoid damaging this equipment.

1. Ensure all control circuits are disconnected and insulated.
2. Disconnect the conductor on terminal R of the NGRS-XX resistor sensor from the SIGMA-MD monitor relay and 
ensure the conductor is insulated.
3. Disconnected the conductor on terminal G of the NGRS-XX resistor sensor from ground and ensure the 
conductor is insulated.
4. Disconnected the conductors between the X1 and X2 terminals of the TxA type ZSCS and the SIGMA-MD monitor 
relay and ensure these conductors are insulated.
5. Disconnect the control power leads from the SIGMA-MD monitor relay and ensure these conductors are insulated.
6. Connect short conductors between the L, N and G terminals of the SIGMA-MD monitor relay ensuring that the G 
terminal remains connected to ground.
7. Perform the high-pot or dielectric withstand tests required.
8. Reconnect the conductors between the X1 and X2 terminals of the TxA type ZSCS and the SIGMA-MD 
monitor relay.
9. Reconnect the conductor between terminal G of the NGRS-XX resistor sensor and the appropriate terminal on the 
SIGMA-MD monitor relay. Refer to Figure 2.
10. Reconnect the conductor from the G terminal on the NGRS-XX resistor sensor to ground.
11. Remove the conductors added between the L, N and G terminals of the
SIGMA-MD monitor relay ensuring that the G terminal remains connected to ground.
12. Reconnect the conductor from the R terminal of the NGRS-XX resistor sensor to the appropriate terminal of the 
SIGMA-MD monitor relay. Refer to Figure 2.
13. Reconnect and control circuits which were disconnected in step 1.
14. Reconnect the control power to the L and N terminals of the SIGMA-MD monitor relay.

Summary of Contents for SIGMA-MD

Page 1: ...C EG42EM Instruction Manual December 2018 Previously C 455EM GROUND FAULT RELAY NEUTRAL GROUNDING RESISTOR SIGMA MD...

Page 2: ...s 10 6 1 Start Up and Reset Indications 10 6 2 Power on Led Green 11 6 3 Ground Fault Led Red 11 6 4 NGR Fault Led Red 11 6 5 Zone Ground Led Red 12 7 Self Test 12 8 Relay Settings 13 8 1 Trip Relay O...

Page 3: ...omer service and technical leadership We build on this foundation by investing in developing new products in electrical safety education including EFC scholarship program by actively participating in...

Page 4: ...present Hazard of Electrical Shock Burn or Explosion All installation servicing and testing referred to in this manual must be performed by qualified personnel All power should be disconnected prior...

Page 5: ...minal value When the ZSCS current is below 1 of the NGR let through current setting the SIGMA MD monitor relay simply monitors the NGR resistance for continuity i e whether the NGR is open or presents...

Page 6: ...fast response is necessary as failure of the NGR implies that there is limited ground fault protection on the system It also ensures fast tripping when a transformer is energized and the resistor is...

Page 7: ...necting the NGRS from the SIGMA MD monitor relay the R terminal of the NGRS should be disconnected BEFORE the Ground connection is removed from the G terminal of the SIGMA MD monitor relay The procedu...

Page 8: ...e trip relay terminals the auxiliary fault relay terminals the external reset test and the G F meter terminals If door panel mounted or remote test and or reset controls are required connect momentary...

Page 9: ...MD MONITOR RELAY AND NGR The SIGMA MD monitor relay has settings for the let through current ground fault trip current level and ground fault time delay These settings may be specified in the installa...

Page 10: ...r if the SIGMA MD processor fails this normally closed relay will open The contacts will close when the power LED turns on and remain closed as long as the relay is operating correctly All relays are...

Page 11: ...et flashing The trip relay auxiliary fault relays and associated LED will remain as such indefinitely regardless of whether a fault is present on the system and until the conditions which caused the t...

Page 12: ...l be ON when the SIGMA MD monitor relay has detected and qualified a ground fault The RED GND FAULT LED will remain ON until the SIGMA MD monitor relay is manually reset even if the NGR fault conditio...

Page 13: ...GMA MD monitor relay and no voltage applied to system transformer s primary winding Alternatively the system transformer s primary winding may be powered with the system transformer secondary isolated...

Page 14: ...en control voltage is applied to the SIGMA MD monitor relay and the system is operating normally The trip relay is energized trip when the measured values of the ground fault current or NGR resistance...

Page 15: ...A MD monitor relay will resume monitoring of the system and if a fault remains on the system will detect the fault and will re trip de energizing the trip relay 8 2 TRIP MEMORY SETTING The SIGMA MD mo...

Page 16: ...ble and not higher than 20 when complying with this CSA Mine Safety Standard 8 5 SYSTEM FREQUENCY The SIGMA MD monitor relay has two settings for selecting the AC frequency of the system it monitoring...

Page 17: ...is Idle Not Tripped Trip Relay is not energized Aux Fault Relays are not energized DOWN SIGMA MD Relay is Tripped Trip Relay is energized Aux Fault Relays are energized MODE DIP SWITCH SETTING Table 1...

Page 18: ...U U D 1550 D U U U U 1650 U D D D D 1750 U D D D U 1850 U D D U D 1950 U D D U U 2050 U D U D D 2150 U D U D U 2250 U D U U D 2350 U D U U U 2450 U U D D D 2550 U U D D U 2650 U U D U D 2750 U U D U U...

Page 19: ...y U UP D DOWN Table 4 Ground Fault Trip Current Level Settings SYSTEM FREQUENCY 60 50 Hz DIP SWITCH SETTING SYSTEM FREQUENCY 50 Hz UP SYSTEM FREQUENCY 60 Hz DOWN DIP switch 11 right hand array U UP D...

Page 20: ...CS 550 U D U D I GARD TxA Type ZSCS 600 U D U U I GARD TxA Type ZSCS 650 U U D D I GARD TxA Type ZSCS 700 U U D U I GARD TxA Type ZSCS 750 U U U D I GARD TxA Type ZSCS 800 U U U U I GARD TxA Type ZSCS...

Page 21: ...restored after a loss of control power the trip relay and auxiliary fault relays are returned to the state these relays had prior to the loss of control power The state of the trip relay and auxiliary...

Page 22: ...s open or presents some resistance Trip Time Less than 60 seconds per CAN CSA M421 00 Typically 3 5 seconds 0 100 msec Up to 10 seconds under certain conditions Accuracy NGR Trip Resistance limits in...

Page 23: ...the conductor on terminal G of the NGRS XX resistor sensor from ground and ensure the conductor is insulated 4 Disconnected the conductors between the X1 and X2 terminals of the TxA type ZSCS and the...

Page 24: ...in less than 1s if ground fault current exceeds 20 of the prospective ground fault current 3 6 2 Neutral Grounding Devices A neutral grounding device shall be a continuously rated except when ground f...

Page 25: ...24 Figure 2 Sigma MD Monitor Relay Detail A Typical NGRS Sensing Resistor Ngrs 6 Dual Voltage Model Shown Figure 3 Low Voltage NGRS Resistor Sensor...

Page 26: ...25 Figure 5 NGRS 50 Figure 4 NGRS 25...

Page 27: ...26 Figure 6 High Voltage NGRS Resistor Sensors...

Page 28: ...www i gard com Phone 905 673 1553 Toll Free 1 888 737 4787 Fax 905 673 8472 support i gard com...

Reviews: