Important note to consider:
When in Service Mode, the controller does not make any automatic adjustment of the
APV, regardless of any configuration it has received from oNet. As soon as you exit
Service Mode, the APV starts to control automatically from the starting point configured
in the calibration process.
For this reason, it is absolutely vital that the controller is left in service mode when the
shut-off valves on the PRV are opened, to ensure that the APV is still at the same
starting point when it starts to hydraulically control the pressure.
It is only after the pressure has stabilised and the PRV is controlled hydraulically by the
APV that the user should exit Service Mode and allow automatic control to start moving
the APV