i2O
|
www.i2owater.com
|
info@i2owater.com
|
+44 (0) 2380 111 420
Page 6
ii.
Calibration procedure
Before activating the i2O PRV Control System, the following prerequisites must be met:
Verify correct installation of equipment
Control Logger set up
Flow cable connected
Control Logger pre-assigned to a location / associated to a DMA, using the device
serial number in i2O Portal Platform
Start Configurator; Download Configurator from your i2O Platform. For more
information on downloading and using Configurator, visit support.i2owater.com.
Deploy device through Configurator
This updates location/DMA details in the device and imports configuration
settings
Check the flow calibration and adjust as required
Ensure PRV is not under i2O control
Connect
the
Control
Logger to the Laptop and
open Configurator. After a
few seconds, the main
screen of Configurator will
appear
showing
the
different options.
You must be in service
mode in order to calibrate
the APV.
Once in service mode,
select the option “APV
Calibration”