[3] Set parameters as shown below from now. Mode setting should be “Remote net [Ver. 1 mode].”
Parameters different from initial setting are as follows.
・
“Start I/O No”····················I/O address of master unit, 0080
・
“All connect account” ·······Number of remote stations, 2
・
“Remote input (RX) Refresh device” ·············· X100
・
Remote output (RY) ······································· Y100
・
Remote register (RWr)··································· D200
・
Remote register (RWr)··································· D100
・
Special relay (SB) ·········································· SB80
・
Special register (SW) ····································· SW80
Install master station buffer
memory to an internal device
of the PLC-CPU.