2. Specifications
2.1 Interface
Specifications
The table below lists the specifications of the ProfiBus-DP interface.
Item Specification
Remarks
Communication profile
ProfiBus-DP
Communication method
Hybrid method
Master/slave method with token passing
Number of connectable
stations
32 stations per segment
Up to 126 stations can be connected if a
repeater is used.
Communication data length Maximum 244 bytes per frame
Physical profile
RS485
* A general physical profile is RS485.
* Use of a 9-pin D-sub connector is
recommended for IP20 configurations.
Baud rate (kbps)
*1
Maximum distance over the
entire network
Baud rate
Cable type
100 m
12,000/6,000/3,000 kbps
200 m
1,500 kbps
400 m
500 kbps
1000 m
187.5 kbps
Transmission distance
1200 m
9.6/19.2/93.75 kbps
Type A cable
Topology
Bus/tree/star
Cable
Single shielded twisted pair
cable
Type A cable
*1 The baud rate of a ProfiBus-DP network can be specified only when the ProfiBus-DP network is set up using
a configurator (*2).
The baud rate of all ProfiBus-DP slave modules is set with this configurator, and therefore a different baud
rate cannot be set for an individual slave station.
*2 For the ProfiBus-DP configurator, use the configurator recommended for the master unit.
Reference Manufacturer
Software name
(As of March 13, 2001)