background image

iAIRE 

ION Kit I/O/M

iAIRE, LLC

11

Mount the wall plate first. Place the detector against the wall at the desired location. The wires must be able to pass through the notch

on the wall plate. Reference figure 1 for dimensions.

Connect wires to terminal strips, (see the label on the wall plate and fig.3). Make sure wiring connection is correct and secure.

 

The  transmitter  has  been  set  at  0~10VDC  analog  output  before  leaving  the  factory.  If  you  want  to  change  the  output  voltage,  please 
operate  as  noted  in  the  table  below:  Cut  off  power  and  simultaneously  depress  the  2  clips  on  either  of  the  sides  of  the  transmitter  to 
remove the faceplate from the wall plate. There are four jumpers on the top left of circuit (S1, S2, J1, J2) and choose a different output 
voltage through disconnection or connection as noted in the table below. 

Analog output and Corresponding VOC Values 

Note: 

When you test and install the transmitter, please take 

notice that it should be placed perpendicular to the ground 
and keep head-on. Because the air hole is at the bottom of 
the product, incorrect placement can affect the test result. 

 

Electrical Data 

G+ 

Power (+) 

24VAC/24VDC + 

G0 

Power ground (-) 

24VAC/24VDC 

OUT 

Analog output (+) 

0~10VDC (default) 

RS485 interface 

9600/14400/19200(default)/28800/38400bps  (programmable  selection), 
15KV antistatic protection.   

S2 

S1 

J1 

J2 

Analog Output 

Upper two pins connection 

Upper two pins connection 

connection 

Un-effective 

4mA~20mA 

Upper two pins connection 

Upper two pins connection 

disconnection 

Un-effective 

No analog output 

Below two pins connection 

Below two pins connection 

connection

  

connection

1VDC~5VDC

Below two pins connection 

Below two pins connection 

connection 

disconnection 

2VDC~10VDC 

Below two pins connection 

Below two pins connection 

disconnection

 

connection

0~5VDC

Below two pins connection 

Below two pins connection 

disconnection 

disconnection 

0~10VDC 

Figure.3 connection

 

7

0~10VDC Analog Output 

Indoor Air Quality 

good

poor

SEN-0071

6

5

Connection Terminal  Function 

6
7

ON 
OP 

Alarm output 
Alarm Common

0/2-10VDC

or 0/4-20mA

0V

10V

0ppm      5ppm       10ppm     15ppm    20ppm    25ppm     30ppm

Mount the wall plate first. Place the detector against the wall at the desired location. The wires must be able to pass through the notch

on the wall plate. Reference figure 1 for dimensions.

Connect wires to terminal strips, (see the label on the wall plate and fig.3). Make sure wiring connection is correct and secure.

Select the Voltage of Output 

Follow the steps in figure 4 to close the cover.

Figure . 4 closing steps

 

Page 

2

iAIRE | www.my

ultrapure

.com | 

844-348-9168

Summary of Contents for ION KIT Series

Page 1: ...ION XX KIT I O M Manual PD 04 20 2023 v 01 16 PN IOM 0022...

Page 2: ...it I O M 2 Table of Contents ION Kit Overview 3 Package Submittal 4 Installation and Operational Notes 5 Ion Install Kit Wiring 6 Ion Generator Submittal 8 Ion Generator Installation 9 SEN 0071 VOC Se...

Page 3: ...vironment size the Ion Kit to perform at 2500 CFM per block However if you are in a smoking or a fried food environment each ionization block will only do 1 250 CFM block Be sure to size your ionizati...

Page 4: ...re Ion devices UL 867 CSA C22 2 File 101141865COL 003 iAIRE LLC 2100 Consulate Drive Suite 102 Orlando FL 32837 www myultrapure com Toll Free 844 348 9168 SUB 0002 PD 04 20 2023 v 1 21 Part Ion Genera...

Page 5: ...p The Ion Kit gets power from the existing 24V power in the HVAC unit if there are 3 or less ion generators If there are 4 or more ion generators 24V power supplies are provided and need to be install...

Page 6: ...VAC 240VAC 480VAC BLK WHT RED ORG BLK RED F FI IG GU UR RE E 3 3 YEL BLUE COMMON 120VAC 208VAC 240VAC 480VAC BLK WHT RED ORG BLK RED YEL BLUE TRANSFORMER 2 2 TRANSFORMER 3 3 1 24VAC VDC 2 G 24VAC VDC...

Page 7: ...iAIRE ION Kit I O M iAIRE LLC 7 The following are reference product installation sheets...

Page 8: ...Homes Schools Animal Feeding and Processing Plants Shopping Malls Laboratories Veterinary Offices Restaurants and Food Preparation Areas Zoos Casinos Convention Centers and Arenas Jails Museums Health...

Page 9: ...urface to prevent arcing The ion air purifier has two mounting flanges with a hole to accommodate 1 8 self tapping sheet metal screws figure 1 1 With the provided metal screws mount the ion air purifi...

Page 10: ...in figure 2 Then slant the screwdriver and gently separate the cover from the wall plate by following steps 2 through 4 60 0 0 45 00 55 00 28 0 0 3 0 0 4 5 0 8 0 0 Figure 1 l SEN 0071 Indoor Air Qual...

Page 11: ...log output 0 10VDC default 4 B RS485 interface 9600 14400 19200 default 28800 38400bps programmable selection 15KV antistatic protection 5 A S2 S1 J1 J2 Analog Output Upper two pins connection Upper t...

Page 12: ...pm VOC measurement 10ppm 1st yellow light on when 10ppm VOC measurement 15ppm 1st and 2nd yellow lights on when 15ppm VOC measurement 20ppm 1st red light on when 20ppm VOC measurement 25ppm 1st and 2n...

Reviews: