background image

iAIRE, LLC

iAIRE 

ION Kit I/O/M

6

SSCCHH--IIO

ONN--00000033

IIO

ONN  FFIIEELLDD  IINNSSTTAALLLL  KKIITT  W

WIIRRIINNG

G

X

C

G

W2

W1

Y2

Y1

R

CENTRAL TERMINAL 

BOARD

  oorr  CC..TT..BB

 

(existing)

C

BLK

GRN

R

RED

REQUIRED 24 VAC 

TRANSFORMER IF 

OR 

MORE ION DEVICES

BLK

GRN

BLK

GRN

BLK

GRN

CONNECT  

POWER HERE IF 

INSTALLING 4 

OR LESS ION 

DEVICES

CONNECT  POWER HERE 

IF INSTALLING 5 OR 

MORE ION DEVICES

IIO

ONN

DDeevviiccee  11

IIO

ONN  

DDeevviiccee  22

IIO

ONN  

DDeevviiccee  33

IIO

ONN  

DDeevviiccee  44

IIO

ONN  

DDeevviiccee  55

IIO

ONN  

DDeevviiccee  66

BB==BBllaacckk  W

Wiirree

RR==RReedd  W

Wiirree

TERMINAL

STRIP

(T1)

1

2

3

4

5

6

7

8

9

10

11

12

BLK

RED

TERMINAL

STRIP

(T3)

1

2

3

4

5

6

7

8

9

10

11

12

RED

B1

B2

B3

B4

B5

B6

R1

R3

R3

R4

R5

R6

B7

B8

B9

B10

B11

B12

R7

R8

R9

R10

R11

R12

FFIIG

GUURREE  11

BLK

BLK

RED

BLK

BLK

TO NEXT TERMINAL 

STRIP IF NEEDED

COMMON

120VAC

208VAC

240VAC

480VAC

BLK

WHT

RED

ORG

BLK / RED

FFIIG

GUURREE  33

YEL

BLUE

COMMON

120VAC

208VAC

240VAC

480VAC

BLK

WHT

RED

ORG

BLK / RED

YEL

BLUE

TRANSFORMER

  22

TRANSFORMER

  33

1

+

24VAC/VDC

2

G

24VAC/VDC

1

0,2-10VDC

2

4

3

A

RS-485

5

VVO

OCC  SSEENNSSO

ORR

B

R

RED

CC

RED

FFIIG

GUURREE  22

DETERMINING QUANTITY 

OF TRANSFORMERS

0 - 

3

   ION DEVICES = USE FACTORY C.T.B.

 

4

 - 14 ION DEVICES = 1 TRANSFORMER

 

15-

28

 ION DEVICES = 2 TRANSFORMERS

29

-40 ION DEVICES = 3 TRANSFORMERS

B1

R1

R2

R3

R4

R5

B2

B3

B4

B5

R6

B6

NNO

OTTEE    11::   

EACH TERMINAL STRIP CAN HANDLE A MAXIMUM OF SIX 

IONIZATION DEVICES 

NNO

OTTEE  22::  

SEE FIGURE 1 FOR PROPERLY WIRING WHEN ADDING 

ADDITIONAL TERMINAL STRIPS FOR ADDITIONAL IONIZATION DEVICES. IF 

EXCEEDING 2 IONIZATION TERMINAL STRIPS, WIRE EACH ADDITIONAL 

TERMINAL STRIP TO PREVIOUS TERMINAL STRIP IN SAME MANNER AS 

FIGURE 1 WAS ADDED TO TERMINAL STRIP (TS 1)

NNO

OTTEE  33:: 

SEE FIGURE 2 FOR PROPER QUANTITY OF TRANSFORMERS FOR 

QUANTITY IF IONIZATION DEVICES

NNO

OTTEE  44:: 

SEE FIGURE 3 FOR PROPER WIRING OF TRANSFORMERS WHEN 

ADDING IONIZATION DEVICES IN TO MATCH FIGURE 2 (MUST WIRE 24 VAC 

IN PARALLEL)

Revision: V01.02

Summary of Contents for ION KIT Series

Page 1: ...ION XX KIT I O M Manual PD 04 20 2023 v 01 16 PN IOM 0022...

Page 2: ...it I O M 2 Table of Contents ION Kit Overview 3 Package Submittal 4 Installation and Operational Notes 5 Ion Install Kit Wiring 6 Ion Generator Submittal 8 Ion Generator Installation 9 SEN 0071 VOC Se...

Page 3: ...vironment size the Ion Kit to perform at 2500 CFM per block However if you are in a smoking or a fried food environment each ionization block will only do 1 250 CFM block Be sure to size your ionizati...

Page 4: ...re Ion devices UL 867 CSA C22 2 File 101141865COL 003 iAIRE LLC 2100 Consulate Drive Suite 102 Orlando FL 32837 www myultrapure com Toll Free 844 348 9168 SUB 0002 PD 04 20 2023 v 1 21 Part Ion Genera...

Page 5: ...p The Ion Kit gets power from the existing 24V power in the HVAC unit if there are 3 or less ion generators If there are 4 or more ion generators 24V power supplies are provided and need to be install...

Page 6: ...VAC 240VAC 480VAC BLK WHT RED ORG BLK RED F FI IG GU UR RE E 3 3 YEL BLUE COMMON 120VAC 208VAC 240VAC 480VAC BLK WHT RED ORG BLK RED YEL BLUE TRANSFORMER 2 2 TRANSFORMER 3 3 1 24VAC VDC 2 G 24VAC VDC...

Page 7: ...iAIRE ION Kit I O M iAIRE LLC 7 The following are reference product installation sheets...

Page 8: ...Homes Schools Animal Feeding and Processing Plants Shopping Malls Laboratories Veterinary Offices Restaurants and Food Preparation Areas Zoos Casinos Convention Centers and Arenas Jails Museums Health...

Page 9: ...urface to prevent arcing The ion air purifier has two mounting flanges with a hole to accommodate 1 8 self tapping sheet metal screws figure 1 1 With the provided metal screws mount the ion air purifi...

Page 10: ...in figure 2 Then slant the screwdriver and gently separate the cover from the wall plate by following steps 2 through 4 60 0 0 45 00 55 00 28 0 0 3 0 0 4 5 0 8 0 0 Figure 1 l SEN 0071 Indoor Air Qual...

Page 11: ...log output 0 10VDC default 4 B RS485 interface 9600 14400 19200 default 28800 38400bps programmable selection 15KV antistatic protection 5 A S2 S1 J1 J2 Analog Output Upper two pins connection Upper t...

Page 12: ...pm VOC measurement 10ppm 1st yellow light on when 10ppm VOC measurement 15ppm 1st and 2nd yellow lights on when 15ppm VOC measurement 20ppm 1st red light on when 20ppm VOC measurement 25ppm 1st and 2n...

Reviews: