9.1.4
Diagnosis
The most important diagnostic features are an integrated part of the I/O manager in
ibaPDA-V6.
The main branch
General
in the tree view, tab
Interrupt Info
, shows the interrupt counter.
The counter iba-Interrupts must have 1000 increments per second! If not, the interrupt
master is missing. In this case check the card settings.
In the dialog box of the link level (see 9.1.1), tab
Info
, you can see if the communication
between ibaFOB card and ibaPADU device is working by checking the baud rate value. A
stable baud rate means that the communication is working well. An alternating baud rate
indicates that the link is broken or the ibaPADU device is off.
When exiting the I/O manager by pressing OK the system performs a consistency check
of the configuration. If the configuration is valid it will be applied.
For a detailed description of the system configuration please refer to the corresponding
manuals of our software products ibaPDA, ibaLogic or ibaScope.