ibaPADU-S-IT-16
Manual
Issue 1.10
23
The devices are addressed via the S1 rotary switch
Device number in the
cascade
Position of rotary switch S1
1
st
device
1
2
nd
device
2
…
…
14
th
device
E
15
th
device
F
A cascade can be formed with all devices that support the ibaNet 32Mbit Flex protocol. At
the moment, these are the following devices:
ibaBM-DDCS
ibaBM-eCAT
ibaBM-SiLink
ibaPADU-S-CM
ibaPADU-S-IT-16
8.3
Supported ibaNet transfer protocols
Protocol
Position of
the rotary
switch S1
Min. telegram
cycle (Tcycl)
Max. signal
sampling
frequency
Direction of
communica-
tion
x-directional
Max. data volume
(in bytes)
Max. number
of participants
in FO ring to-
pology
ibaNet
3Mbit
0
1
1 ms
1 kHz
uni
136 B
(64 Integer-,
64 binary values)
8
ibaNet
32Mbit
50µs
0
1
50 µs
20 kHz
uni
144 B
(64 Integer-,
64 binary values)
1
ibaNet
32Mbit
100µs
0
1
100 µs
10 kHz
uni
288 B
(128 Integer,
128 binary values)
1
ibaNet
32Mbit
1000µs
0
1
1 ms
1 kHz
uni
2304B
(1024 Integer-,
1024 binary values)
or
(512 Real-,
512 binary values)
1
ibaNet
32Mbit
Flex
1 … F
Min. 25 µs
Max. 40 kHz
bi
72B at 25µs T
cycl
3147B at 1ms T
cycl
15
1
Only in combination with ibaLogic