6. Specifications
MODEL
iBall Nirantar Online UPS
1006B
(1KVA - W Battery)
1012E
(1KVA - W/O Battery)
3001E
(3KVA - W/O Battery)
INPUT
Capacity
1000 VA / 800 W
3000 VA / 2400 W
Voltage
Range
Low Line Transfer
160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 %
( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
Low Line Comeback
168 VAC / 148 VAC / 128VAC / 118 VAC ± 5 %
( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
High Line Transfer
300 VAC ± 5 % or 150 VAC ± 5 %
High Line Comeback
290 VAC ± 5 % or 145 VAC ± 5 %
Frequency Range
40Hz ~ 70 Hz
Phase
Single phase with ground
Power Factor
≧
0.99 @ Nominal Voltage (Full load)
OUTPUT
Output Voltage
200/208/220/230/240VAC
Voltage Regulation
± 1%
Frequency Range (Synchronized Range)
47~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode)
50 Hz ± 0.2 Hz or 60Hz ± 0.2 Hz
Current Crest Ratio
3:1
Harmonic Distortion
≦
2 % THD (Linear Load)
≦
4 % THD (Non-linear Load)
Transfer
Time
AC to DC
Zero
Inverter to Bypass
4 ms (Typical)
Waveform (Batt. Mode)
Pure Sinewave
EFFICIENCY
To AC Mode
87%
90%
To Battery Mode
83%
89%
BATTERY
Battery Type
12 V / 9 AH
NA
NA
Numbers
3
3
6
Typical Recharge Time
4 hours recover to
90% capacity
Depending on the capacity of external batteries
Charging Current (max.)
1.0 A
1.0A/2.0A/4.0A/6.0 A
Charging Voltage
41.0VDC ± 1%
82.1 VDC ±1%
INDICATORS
LCD or LED
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault
indicators
ALARM