background image

AST0715MP-960

 

Page 18 

20/11/2006

 

 

 

When the green light is on next to the TIME OF DAY 
legend, the display is showing the time that the 
control thinks it is correct. If you need to change the 
Time of Day, refer to the instructions later in this 
section. The Time of Day displays time in hours and 
minutes sepa-rated by a colon[:]. When the colon is 
flashing on and off, water is flowing through the 
conditioner. There is a small red dot in the upper left 
corner near the PM letters to indicate PM for 12-hour 
clocks. When the dot is off, the time is AM. You can 
set the clock for any time, AM or PM. 

  

Complete the following steps to change the Time of 
Day: 
1.  Press the down arrow 

ò

 button until the green 

light next to the TIME OF DAY legend is on. 

2.  Press the 

SET

 button and the minute number on 

the display starts flashing. If you want to change 
this number , press the up arrow 

ñ

 button to 

increase the number or the down arrow 

ò

 button 

to decrease the number. To skip the number 
without changing, press the left arrow 

ï

 button. 

3.  When the number is correct, press the left arrow 

ï

 button. The first number stops and the next 

number starts flashing. You can only change the 
flashing number. 

4.  Continue changing numbers until you reach the 

desired setting. 

5.  Press the 

SET

 button. The number stops flashing 

and the control accepts the new setting. After 
approximately 30 seconds, the control starts alter-
nating the display between TIME OF DAY and 
CAPACITY. 

Note: 

If a beep sounds, the new setting is not 

accepted. 
 

Reminder: 

The control does not keep time during a 

power outage but will resume its timekeeping from the 
time of day power was lost. A short power outage 
should not cause a problem. If the outage is several 
hours, the control will regenerate at the wrong time of 
day. All other memory is stored in the NOVRAM and 
maintained during power outage. Refer to page3. 
 

Time of Regeneration 

 
The control uses the Time of Regeneration to decide 
when to begin a regeneration. When a regeneration is 
necessary and the Time of Day Clock is at the same 
time as the Time of Regeneration setting, the control 
starts the regeneration. The factory setting for Time of 
Regeneration is 2:00 AM. If this time is inconvenient, 
you can select any other time of day. Remember that 
the soft water is not available during a regeneration of 
the water conditioner. Time of Regeneration can be 
set for any time, AM or PM. 
 

Note: 

The control may be programmed for an immed-

iate regeneration option. In this case, the control does 
not wait for the Time of Regeneration but regenerates 

when the remaining capacity reaches zero. Contact 
your dealer for more information regarding this option. 
 
Complete the following steps to change the Time of 
Regeneration: 
1.  Press the down arrow 

ò

button until the green 

light next to the TIME OF REGEN legend is on. 

2.  Press the 

SET 

button and the minute number on 

the display starts flashing. If you want to change 
this number, press the up 

ñ

 button to increase 

the number or the down arrow 

ò

 button to 

decrease the number. 
To skip the number without changing, press the 
left arrow 

ï

 button. 

3.  When the number is correct, press the left arrow 

ï

 button. The first number stops flashing and the 

next number starts flashing. You can only change 
the flashing number. 

4.  Continue changing numbers until you reach the 

desired setting. 

5.  Press the 

SET

 button. The number stops flashing 

and the control accepts the new setting. After 
approximately 30 seconds, the control starts alter-
nating the display between TIME OF DAY and 
CAPACITY. 

Note: 

If a beep sounds, the new setting is not 

accepted. 
 

Hardness Setting  

 
The Hardness Setting refers to the amount of hard-
ness

 

minerals in your water before it is conditioned. 

The control uses this setting to calculate how many 
gallons of water can be conditioned before a 
regeneration is necessary. 
Your water treatment dealer tested the water at the 
time of installation and entered a Hardness Setting in 
the control. We recommend that you consult your 
dealer or have your water retested before changing 
this setting 
You can see the Hardness Setting the dealer entered 
by pressing the down arrow 

ò

 button until the green 

light next to the HARDNESS legend is on. The 
number on the display is the measure of water 
hardness in grains per gallon (milligrams per litre for 
metric). 
 
Complete the following steps to change the Hardness 
Setting: 
1.  Press the down arrow 

ò

button until the green 

light next to the HARDNESS legend is on. The 
setting range is (30 TO 2500 milligrams/litre for 
metric) 

2.  Press the 

SET 

button and the minute number on 

the display starts flashing. If you want to change 
this number, press the up 

ñ

 button to increase 

the number or the down arrow 

ò

 button to 

decrease the number. 
To skip the number without changing, press the 
left arrow 

ï

 button. 

Summary of Contents for AST0715MP-960

Page 1: ...ON OPERATING INSTRUCTIONS Model AST0715MP 960 Serial No Telephone 07 3219 2233 Facsimile 07 3219 2266 Email sales ibcwater com au Website www ibcwater com au FILTRATION WATER TREATMENT PRODUCTS for co...

Page 2: ...15 25 12 15 27 0 70 0 70 1 2 Peak flow not recommended for extended periods of time Brine Tank Poly moulded construction complete with lid Operating Pressure 205 690 kPa Temperature 5o x 50o C Electr...

Page 3: ...H THE TOP STRAINER SUPPLIED LOOSE IT IS IMPORTANT THAT THIS STRAINER IS ASSEMBLED TO THE VALVE DURING INSTALLATION THE LENGTH OF THE INTERNAL RISER PIPE IS FACTORY ADJUSTED FOR THE TANK SIZE PROVIDED...

Page 4: ...Programming For your Application Units of Measure Notes P1 Time of day AM or PM 1 00 to 12 59 1 Current time Hour minute Range depends on value selected for P13 Enter the current time P2 Time of day O...

Page 5: ...as per Instruction Booklet page 16 figure 3 For the drain line connection to the valve a 15mm hose tailpiece is supplied loose in the carton STEP 2 Remove from cabinet and remove polystyrene packing...

Page 6: ...nded The following will have to be programmed into the control Current time of day Hardness of your local water supply Plug transformer into main GPO Push lead end into socket underneath the front of...

Page 7: ...k Using the buttons key in the current second hour figure In example 11 25 Key in 1 Press the key the first hour digit will blink Using the buttons key in the first hour figure In example 11 25 Key in...

Page 8: ...k Using the button only keep on pressing slowly until a little dot appears in the top left hand corner of the display under PM if the display is blinking and shows 1 keep on pressing button until 0 ap...

Page 9: ...eck the settings in the program wait till the green light moves to TIME OF DAY Check time of day is correct Press button to TIME OF REGENERATION 2 00 should be displayed Press button to HARDNESS the h...

Page 10: ...r is being expelled along with the water close off the mains water inlet valve Slowly turn the camshaft anti clockwise till the white line in the round window comes around to the REFILL position Turn...

Page 11: ...brine tank or cabinet will be refilled with the correct amount of water necessary to dissolve the salt required Open the outlet mains valve and close off the bypass valve and check the treated water...

Page 12: ...AST0715MP 960 Page 12 20 11 2006 Water Conditioning Control System Installation Operating and Maintenance Manual Series 255 Valve 960 Control...

Page 13: ...eneration Manual Regeneration Care of Your Water Conditioner 20 General Cleaning the Injector Injector Screen Maintaining the Drain Line Manual Valve Operation 22 Additional Features 22 Disinfection o...

Page 14: ...free performance The metering system has only one moving part a rotating turbine that measures water usage Time and Capacity Display During normal conditioning operation the correct time of day altern...

Page 15: ...held closed by water pressure and are leak tight Valve seats are in a vertical position which is the position least vulnerable to plugging System operation cannot get out of phase or sequence The con...

Page 16: ...ts Water Line Connection A bypass valve system must be installed to provide for occasions when the water conditioner must is by passed for hard water or for servicing The most common bypass systems ar...

Page 17: ...ay freezes with the REGEN TIME REMAINING information After the first regeneration is completed the second regeneration begins immediately The display will alternate between the TIME OF DAY and REGEN T...

Page 18: ...ing a regeneration of the water conditioner Time of Regeneration can be set for any time AM or PM Note The control may be programmed for an immed iate regeneration option In this case the control does...

Page 19: ...bers until you reach the desired setting 5 Press the SET button The number stops flashing and the control accepts the new setting After approximately 30 seconds the control starts alter nating the dis...

Page 20: ...his setting your dealer has disabled it Some municipalities require that the Salt Setting not be adjustable Contact your dealer for additional information Capacity Setting The Capacity Setting refers...

Page 21: ...in this manual or contact your dealer for more information about these options The factory setting for Time of Regeneration is 2 00 AM You can change this time Refer to the Time of Regeneration secti...

Page 22: ...caution note 12 Reinstall cover reconnect electric power and reset the time of day 13 Slowly open the water supply valve or return the bypass valve s to the not in bypass position Maintaining the Drai...

Page 23: ...option is a method of forcing the control to regenerate after a preset number of days is normal demand based regeneration does not occur first This feature is not set at the factory your dealer can se...

Page 24: ...used to treat potable water Refer to the Disinfection of Water Conditioners section in this manual Complete the following steps to place the conditioner into operation 1 Remove the rear valve cover by...

Page 25: ...ats refer to the Troubleshooting section in this manual When the water is being drawn fro the brine tank rotate the camshaft COUNTERCLOCKWISE until the indicator points to REGEN COMPLETE Run water fro...

Page 26: ...er Tank 1000215 No 14 for 14 in Diameter Tank 7 1030502 Ball Flow Control 1 8 Injector Assy With O rings 1 1032970 A Injector White 1032971 B Injector Blue 1032972 C Injector Red 9 Injector Cap With O...

Page 27: ...AST0715MP 960 Page 27 20 11 2006 C Meter Adapter Bypass Valve and Piping Boss Bypass Valve 3 960 Control...

Page 28: ...611 3 4 in BSPT Brass Pipe Adaptor Kit 1 1001610 1 in NPT Brass Pipe Adaptor Kit 1 1001612 1 in BSPT Brass Pipe Adaptor Kit 1 Not Shown Code Part No Description Qty Piping Boss 1 Kit Piping Boss Inclu...

Page 29: ...nic Failure Improper start of regeneration limit switch closed when it should be open Improper finish of regeneration limit switch open when it should be closed Improper control settings Cause Control...

Page 30: ...Loss of power to the system a Transformer unplugged b Fuse blown circuit breaker open or circuit switched off a Connect the power b Correct the electrical problem 4 Control does not regenerate automa...

Page 31: ...alent Manual Regeneration Guest Cycle Forces the control to regenerate by pressing the REGEN button Regeneration Includes the backwash brine draw and fresh water rinse steps necessary to prepare the r...

Page 32: ...AST0715MP 960 Page 32 20 11 2006...

Page 33: ...of approximately 20ppm based on a sample volume of 10mls Other hardness test kits are available for more accurate testing eg Hardness Tablets Directions Take a 50ml sample of water in a screw capped b...

Reviews: