background image

AST1052TMP-960

 

Page 14

 

20/11/2006

 

 

 

Introduction

The Model 960 Control provides sophisticated, 
demand-based water conditioning by incorporating a 
microprocessor and a water meter to electronically 
monitor the amount of water used daily. Each day, at 
Time of Regeneration, the control determine if the 
capacity remaining is sufficient to provide conditioned  
Water for the next day. If the remaining capacity is 
too small, the control automatically regenerates the 
resin bed. 
 
 If water usage changes, the computer automatically  
compensates for the change and regenerates as 
needed. Regeneration based on actual water usage. 
The control provides efficient, trouble-free, uninter-
rupted soft water luxury. 
 
The Series 255 valve combines design simplicity with 
glass reinforced NORYL* plastic construction to 
provide an uncommonly reliable appliance. 
 
If maintenance becomes necessary, the Model 960 
Series 255 water Conditioner System offer a unique 
"separation" capability for quick repairs. 
 
NORYL is a trademark of GE Plastics. 
 

Special Features 

 

 

Memory Retention. 

During a power outage, 

critical operating information in the control's 
memory is stored in a special electronic device 
called a NOVARAM. This information includes the 
time of day, water usage amounts, daily average 
water usage, all programming data and the 
number of days since the last regeneration. When 
power is restored, the information is re-turned to 
the microprocessor and operation resumes as if 
an outage never occurred. The time of day will be 
late by the length of the power outage. Because 
most power outages are less than one minute in 
duration, it may be months or years before the 
time display requires resetting. If an outage of one 
or more hours occurs, the time of day should be 
reset but no other reprogramming is necessary. 

 

Design Reliability. 

Solid-state electronics assure 

many years of trouble-free performance. The 
metering system has only one moving part; a 
rotating turbine that measures water usage. 

 

Time and Capacity Display. 

During normal 

conditioning operation, the correct time of day 
alternates with capacity on the display. The 
capacity value is the number of gallons (cubic 
meters of metric units) of water that the unit can 
condition before another regeneration is needed. 

 

Flow indicator. 

The colon between the hours and 

the minutes in the Time of Day display flashes to 
indicate the flow of service water through the 

valve. This provides an easy determination of 
proper meter operation. 

 

Hardness and Capacity Settings. 

Once the 

hardness and capacity settings are entered, the 
information cannot be lost due to a power outage, 
so reprogramming is not necessary.

 

 

Guest Cycle. 

An extra regeneration can be 

achieved at any time by pressing the REGEN 
button on the front panel. It takes a few minutes 
for the regeneration to start. The unit completes 
the regeneration in about two hours. This feature 
is beneficial when you expect to use more than 
the normal amount of water; for example, guest 
visits or an extra heavy laundry day.

 

 

General Conditioner Information 

 

How you're Conditioner Works 

 

In general, your water conditioner works in the follow-
ing manner. Hard water flows into the conditioner and 
through the resin bed where calcium and magnesium 
hardness minerals are exchange. The conditioned 
water flows out of the resin bed into your plumbing 
system. After a certain amount of hard water has 
passed through the conditioner, the resin cannot 
remove any more minerals. This resin state is called 
exhaustion and indicates that the resin needs to be 
regenerated. The regeneration process restores the 
conditioner's ability to soften water. The control 
monitors the amount of water that flows through the 
conditioner and automatically calculates when to 
regenerate the resin bed. 

 

Model 960 Control Front Panel 

 
 
 
 
 
 
 
 
 
 
 
 

The main components of the model 960 Control front 
panel are: 

 

Regeneration Cycle indicator 

 

Green Indicator Lights 

 

Four-Digit Display 

 

 

Figure 1 

Summary of Contents for AST1052TMP-960

Page 1: ...ON OPERATING INSTRUCTIONS Model AST1052TMP 960 Serial No Telephone 07 3219 2233 Facsimile 07 3219 2266 Email sales ibcwater com au Website www ibcwater com au FILTRATION WATER TREATMENT PRODUCTS for c...

Page 2: ...0 12 37 52 25 12 52 70 0 70 0 60 1 58 Peak flow not recommended for extended periods of time Brine Tank Poly moulded construction complete with lid Operating Pressure 205 690 kPa Temperature 5o x 50o...

Page 3: ...TH THE TOP STRAINER SUPPLIED LOOSE IT IS IMPORTANT THAT THIS STRAINER IS ASSEMBLED TO THE VALVE DURING INSTALLATION THE LENGTH OF THE INTERNAL RISER PIPE IS FACTORY ADJUSTED FOR THE TANK SIZE PROVIDED...

Page 4: ...iption Range of Values Min Increments Programming For your Application Units of Measure Notes P1 Time of day AM or PM 1 00 to 12 59 1 Current time Hour minute Range depends on value selected for P13 E...

Page 5: ...erous to walk on STEP 5 Clean top of neck and threads of all traces of resin Remove the plastic cap fitted in Step 3 taking care not to raise the distributor pipe NEVER shorten the length of the distr...

Page 6: ...ended The following will have to be programmed into the control Current time of day Hardness of your local water supply Plug transformer into main GPO Push lead end into socket underneath the front of...

Page 7: ...nk Using the buttons key in the current second hour figure In example 11 25 Key in 1 Press the key the first hour digit will blink Using the buttons key in the first hour figure In example 11 25 Key i...

Page 8: ...nk Using the button only keep on pressing slowly until a little dot appears in the top left hand corner of the display under PM if the display is blinking and shows 1 keep on pressing button until 0 a...

Page 9: ...eck the settings in the program wait till the green light moves to TIME OF DAY Check time of day is correct Press button to TIME OF REGENERATION 2 00 should be displayed Press button to HARDNESS the h...

Page 10: ...ir is being expelled along with the water close off the mains water inlet valve Slowly turn the camshaft anti clockwise till the white line in the round window comes around to the REFILL position Turn...

Page 11: ...brine tank or cabinet will be refilled with the correct amount of water necessary to dissolve the salt required Open the outlet mains valve and close off the bypass valve and check the treated water...

Page 12: ...AST1052TMP 960 Page 12 20 11 2006 Water Conditioning Control System Installation Operating and Maintenance Manual Series 255 Valve 960 Control...

Page 13: ...eneration Manual Regeneration Care of Your Water Conditioner 20 General Cleaning the Injector Injector Screen Maintaining the Drain Line Manual Valve Operation 22 Additional Features 22 Disinfection o...

Page 14: ...free performance The metering system has only one moving part a rotating turbine that measures water usage Time and Capacity Display During normal conditioning operation the correct time of day altern...

Page 15: ...held closed by water pressure and are leak tight Valve seats are in a vertical position which is the position least vulnerable to plugging System operation cannot get out of phase or sequence The con...

Page 16: ...ts Water Line Connection A bypass valve system must be installed to provide for occasions when the water conditioner must is by passed for hard water or for servicing The most common bypass systems ar...

Page 17: ...ay freezes with the REGEN TIME REMAINING information After the first regeneration is completed the second regeneration begins immediately The display will alternate between the TIME OF DAY and REGEN T...

Page 18: ...ring a regeneration of the water conditioner Time of Regeneration can be set for any time AM or PM Note The control may be programmed for an immed iate regeneration option In this case the control doe...

Page 19: ...mbers until you reach the desired setting 5 Press the SET button The number stops flashing and the control accepts the new setting After approximately 30 seconds the control starts alter nating the di...

Page 20: ...this setting your dealer has disabled it Some municipalities require that the Salt Setting not be adjustable Contact your dealer for additional information Capacity Setting The Capacity Setting refers...

Page 21: ...in this manual or contact your dealer for more information about these options The factory setting for Time of Regeneration is 2 00 AM You can change this time Refer to the Time of Regeneration secti...

Page 22: ...caution note 12 Reinstall cover reconnect electric power and reset the time of day 13 Slowly open the water supply valve or return the bypass valve s to the not in bypass position Maintaining the Dra...

Page 23: ...option is a method of forcing the control to regenerate after a preset number of days is normal demand based regeneration does not occur first This feature is not set at the factory your dealer can se...

Page 24: ...used to treat potable water Refer to the Disinfection of Water Conditioners section in this manual Complete the following steps to place the conditioner into operation 1 Remove the rear valve cover by...

Page 25: ...ats refer to the Troubleshooting section in this manual When the water is being drawn fro the brine tank rotate the camshaft COUNTERCLOCKWISE until the indicator points to REGEN COMPLETE Run water fro...

Page 26: ...er Tank 1000215 No 14 for 14 in Diameter Tank 7 1030502 Ball Flow Control 1 8 Injector Assy With O rings 1 1032970 A Injector White 1032971 B Injector Blue 1032972 C Injector Red 9 Injector Cap With O...

Page 27: ...AST1052TMP 960 Page 27 20 11 2006 C Meter Adapter Bypass Valve and Piping Boss Bypass Valve 3 960 Control...

Page 28: ...1611 3 4 in BSPT Brass Pipe Adaptor Kit 1 1001610 1 in NPT Brass Pipe Adaptor Kit 1 1001612 1 in BSPT Brass Pipe Adaptor Kit 1 Not Shown Code Part No Description Qty Piping Boss 1 Kit Piping Boss Incl...

Page 29: ...nic Failure Improper start of regeneration limit switch closed when it should be open Improper finish of regeneration limit switch open when it should be closed Improper control settings Cause Control...

Page 30: ...3 Loss of power to the system a Transformer unplugged b Fuse blown circuit breaker open or circuit switched off a Connect the power b Correct the electrical problem 4 Control does not regenerate autom...

Page 31: ...valent Manual Regeneration Guest Cycle Forces the control to regenerate by pressing the REGEN button Regeneration Includes the backwash brine draw and fresh water rinse steps necessary to prepare the...

Page 32: ...AST1052TMP 960 Page 32 20 11 2006...

Page 33: ...of approximately 20ppm based on a sample volume of 10mls Other hardness test kits are available for more accurate testing eg Hardness Tablets Directions Take a 50ml sample of water in a screw capped b...

Reviews: