background image

5

INSTALLATION AND OPERATION INSTRUCTIONS

IBC INDIRECT WATER HEATERS - ALL MODELS

2) - Pre-Installation Considerations

Inspect shipment carefully for signs of damage. All equipment is carefully 

inspected and packed. IBC’s responsibility ceases upon delivery of the water 

heater to the carrier in good condition. Any claims for damage or shortage, must 

be filed immediately against the carrier by the consignee. No claims for variances 

or shortages will be allowed by the Manufacturer, unless they are presented 

within sixty days after receipt of the equipment.
Installation must conform to the requirements of the authority having jurisdiction. 

In the absence of such requirements, it must conform to the National Plumbing 

Code and the National Electrical Code ANSI/NFPA No. 70, current edition.

IMPORTANT CONSIDERATIONS BEFORE INSTALLATION

1.  Water heater sizing

Choose the water heater model based on the expected water usage for the given 

site. The average residence with one shower or more will require a Model 40 

or larger. The Model 30 should only be considered for residences with minimal 

water demand, or for commercial applications without showers.
Factors that increase water demand dramatically include high flow shower 

heads, hot tubs, and the use of more than one shower at a time. Increase the 

tank size if these factors are present. Carefully review the IBC Water Heater 

specifications contained herein, and consult ASHRAE sizing guides and other 

reliable references.
Dimensions, weights, ratings, and capacities are outlined in Tables 1 and 2.

2.  Boiler sizing

The water heater will provide the rated performance only if it is used with a 

boiler with a heating capacity of at least as much as the capacity ratings in Table 

2. If the boiler has less capacity, the water heating output will be reduced. To 

determine performance with other boiler outputs, refer to the expanded capacity 

tables #6 and #7 in Section 9 of this manual.

3.  Circulator sizing

Refer to Table 2 and table 5 for the flow through the water heater coil and the 

pressure drop at minimum flow. Calculate the pressure drop across all piping and 

fittings connected to the water heater zone. Be sure to include all zone valves, 

check valves, and shut-off valves. It is recommended that the water heater zone 

be piped with 1” pipe around the entire loop on typical residential sites.

A.  System Zone Control

The water heater must be installed as a separate zone from the space heating 

system. The water heating zone’s piping and circulator must be sized for the 

minimum flow rate with all the zones in use and a maximum flow with only the 

water heater in use. This is the reason that the best method of zone control is 

with circulators.
The three most common systems are:
1.  Zone Circulators - The space heating zones use a circulator for each zone, 

and the water heater is controlled with an additional circulator. 

See Section 8, 

Mechanical Drawings #1, #2 and #3.

2.  Hybrid System- The space heating zones use zone valves for each zone, 

and the water heater is controlled with an additional circulator. 

See Section 8, 

Mechanical Drawing #5.

Supplied with this Water Heater: 

The IBC Water Heater is shipped 

with the following items:

1 x 210°F x 150 psig T & P relief 

valve
1 x IBC 10KΩ Temperature sensor
Installation Instructions
Warranty Sheet

NOTE

If this water heater is to be 

installed with a different 

make of boiler than IBC, the 

sensor supplied will not be 

compatible. The temperature 

well in the IBC water heater 

is designed to accept a 

number of different aquastat 

thermostats which can be 

ordered separately. Contact 

your IBC Distributor to order 

an alternate temperature 

controller.

NOTE

There are a number of 

jurisdictional issues that may 

prevent this water heater 

from being accepted by local 

Inspection Authorities. Issues 

such as double-wall heat 

exchanger requirements, 

local or State registration 

requirements, may cause an 

installation to be rejected.
It is essential that the Installer 

check with local Officials 

to ensure acceptance of 

this equipment prior to the 

installation.
IBC will not accept liability 

for any of these situations, 

although we will assist in any 

way we can, in order to help 

gain acceptance. 

Summary of Contents for 30

Page 1: ...IBC 115 HO C FOR SINGLE WATER HEATER INSTALLATIONS For service or repairs to the water heater call your heating contractor Your water heater has been manufactured to provide years of service In order...

Page 2: ...n hazardous conditions that could result in property damage and injury to occupants which in extreme cases might result in death When using electrical appliances basic safety precautions to reduce the...

Page 3: ...es for Hot Water Supply Systems ANSI Z21 22 latest edition This valve must be marked with a maximum set pressure not to exceed the marked working pressure of the water heater Install the valve into an...

Page 4: ...400 14 0 6 6 T P VALVE 1 1 4 NPT BOILER SUPPLY 1 1 4 NPT BOILER RETURN 1 1 2 NPT DOM COLD INLET SENSOR WELL DRAIN C UNITS 8 0 8 0 9 5 3 4 NPT RECIRC PORT 1 1 2 NPT HOT OUTLET T P VALVE BOILER SUPPLY...

Page 5: ...low through the water heater coil and the pressure drop at minimum flow Calculate the pressure drop across all piping and fittings connected to the water heater zone Be sure to include all zone valves...

Page 6: ...software that can provide DHW priority with simultaneous space heating allowed during moderate heating demands C Locating the water heater The water heater should be located in an area where water le...

Page 7: ...supply line to the heater strip back to the tank or nearest mains piping and cap off If oil heating system is to be abandoned completely ensure proper removal and disposal of old oil tank and remainin...

Page 8: ...g system that is either in place or is to be installed for a new hydronic system installation See Schematic drawings in Section 8 for direction 2 It is recommended that minimum size 1 pipe be used on...

Page 9: ...tallation Manual for the boiler as well Temperature Sensor The Temperature Sensor supplied with the IBC Water Heater is an NTC Thermistor type with a resistance of 10 000 ohms at 25 C and 3892 IBC doe...

Page 10: ...HW operation if the DHW Priority setting is higher than the other heating loads Temperature Adjustment The tank sensor controls the maximum water temperature in the water heater If it is set too high...

Page 11: ...e frequent service Depending on water conditions a varying amount of sediment may collect in the tank Levels requiring service are indicated by a small temperature difference between the boiler supply...

Page 12: ...to flush all of the cleaning solution from the tank 11 Reinstall the relief valve and the drain piping 12 Open the cold water supply and fill the tank with water Purge the air from the tank and the pi...

Page 13: ...n Follow steps for Boiler does not operate Check for 24VAC at the zone valve while there is a call for heat if correct voltage is available and connections are good replace the zone valve If the zone...

Page 14: ...with IBC Water Heater Interlock 1 Interlock 2 Therm 1 Therm 2 Therm 3 Outdoor S Indoor S 2nd Loop S DHW S Boiler Net Ext Cont White Green Black Fuse 5A Fuse 5A Fuse 5A Fuse 5A G1 DHW Pump P2 Fan Coil...

Page 15: ...20 115 Pumps Only IBC SL 20 115 BOILER IBC DHW Domestic Hot Water Sensor DHW Pump P1 Fan Coil Pump P2 Outdoor Sensor Fan Coil Thermostat Mechanical Drawing 3 FAN COIL NOTE IBC VFC Series boilers have...

Page 16: ...op S DHW S Boiler Net Ext Cont White Green Black Fuse 5A Fuse 5A Fuse 5A Fuse 5A G1 G2 G3 G4 G5 G6 G7 G8 O1 O2 O3 O4 O5 O6 O7 O8 O9 O10 O11 O12 O13 O14 O15 O16 O17 O18 O19 O20 O21 O22 Auxiliary Interl...

Page 17: ...iping w DHW Pump and Baseboard system Zone Valves Domestic Hot Water Sensor BB Zone 1 Thermostat Mechanical Drawing 5 BB Zone 1 Valve ZV1 BB Zone 2 Valve ZV2 BB Zone 3 Valve ZV3 Zone Valve end switch...

Page 18: ...Well Drain Valve and Temperature Pressure Relief Valve An IBC Temperature Sensor is shipped loose with the tank to be inserted into the Temperature Well and wired to the IBC Boiler Control Board on Te...

Page 19: ...115 F 140 F 115 F 140 F 115 F 140 F 115 F 50 000 139 164 67 92 170 195 67 92 60 000 152 183 80 111 183 214 80 111 80 000 179 219 107 147 210 250 107 147 100 000 205 256 133 184 236 287 133 184 120 000...

Page 20: ...115 F 140 F 115 F 140 F 115 F 140 F 115 F 50 000 139 164 67 92 170 195 67 92 60 000 152 183 80 111 183 214 80 111 80 000 179 219 107 147 210 250 107 147 100 000 205 256 133 184 236 287 133 184 120 000...

Page 21: ...21 INSTALLATION AND OPERATION INSTRUCTIONS IBC INDIRECT WATER HEATERS ALL MODELS DATE LICENSED CONTRACTOR DESCRIPTION OF WORK DONE Service Record Notes...

Page 22: ...ATION AND OPERATION INSTRUCTIONS 22 IBC INDIRECT WATER HEATERS ALL MODELS IBC Technologies Inc 1445 Charles Street Vancouver BC Canada V5L 2S7 Tel 604 877 0277 Fax 604 877 0295 www ibcboiler com 120 1...

Reviews: