Service and maintenance
Inspection of the boiler is to be performed annually by a qualified service technician.
Maintenance checklists
Daily Maintenance
Check
Check the surrounding area – inspect for water leaks in the general area around the boiler and
boiler piping
□
Check the maximum pressure relief valve setting. The heating system pressure should not drop
below 10psi in most applications. If the pressure is outside this normal range or if the water
pressure fluctuates more than 2-3psi, contact your qualified service technician for service.
□
Check the area around the boiler and the air intake opening for obstructions and chemical
contaminates.
□
Monthly Maintenance
Check
Check all the Daily Maintenance items.
□
Check the pressure relief valve and discharge piping for signs of leakage or moisture. If water or
moisture is found, contact your qualified service technician as soon as possible for service.
□
Check the condensate trap and outlet pipe. The condensate trap shall be full of water. The outlet
hose may be connected to a condensate neutralizer, if so, check the pH of the water coming out
of the neutralizer is above 6.0pH. If the pH is below 6.0 then the neutralizer will need to be re-
charged or replaced. Contact your qualified service technician for service.
□
Inspect the flue gas exhaust and air intake connections. All connections should be tight and leak
free.
□
Inspect flue gas exhaust piping, combustion air piping and terminations.
□
9
Service and maintenance