3
INSTALLATION AND OPERATING INSTRUCTIONS
HC SERIES BOILERS
HC 13-50, HC 23-84, HC 29-106, HC 33-124, HC 20-125, HC 33-160
SPECIFICATION
HC 13-50 HC 23-84 HC 29-106 HC 33-124 HC 20-125 HC 33-160
CSA Input (Natural Gas or
Propane) – MBH
13.5 - 51
23 - 84
28.5 - 106
33 - 124
20 - 125
33 - 160
CSA Input (Natural Gas or
Propane) – KW
3.95 - 14.94 6.7 - 24.9
8.4 - 31.0
9.7 - 36.3
5.6 - 36.6
9.7 - 46.9
CSA Output – MBH
12.4 - 45.4
21.2 - 74.8
26.3 - 94.3
30.4 - 110.3
18.6 - 110.8
30.4 - 140.0
CSA Output - KW
3.64 - 13.3
6.2 - 21.9
7.7 - 27.6
8.9 - 32.3
5.4 - 32.5
8.9 - 41.0
A.F.U.E
94%
94%
94%
94%
95%
94%
Min Gas Pressure (Nat. Gas or
Propane) – inch w.c.
5
5
5
5
5
5
Max Gas Pressure (Nat. Gas or
Propane) – inch w.c.
14
14
14
14
14
14
Power (120Vac/60Hz) - Watts @
full fire with internal pump
126
126
128
130
130
164
Weight (empty) – lbs/Kg
85 / 39
85 / 39
85 / 39
85 / 39
85 / 39
85 / 39
Pressure Vessel water content –
USG/Liters
0.37 / 1.4
0.37 / 1.4
0.37 / 1.4
0.5 / 1.9
0.5 / 1.9
0.5 / 1.9
Max boiler flow rate - USgpm
9
9
10
11
11
11
Min boiler flow rate - USgpm
2
2
3
3
3
3
Max Operating Pressure – Space
Heating Coil - psig
43.5
43.5
43.5
43.5
43.5
43.5
Approved installation altitude -
ASL
12,000 ft
12,000 ft
12,000 ft
12,000 ft
12,000 ft
12,000 ft
Ambient Temperature – Low
(°F/°C)
32 / 0
32 / 0
32 / 0
32 / 0
32 / 0
32 / 0
Ambient Temperature – High
(°F/°C)
122 / 50
122 / 50
122 / 50
122 / 50
122 / 50
122 / 50
Max relative humidity (non-
condensing)
90%
90%
90%
90%
90%
90%
Min water Temperature - Space
Heating (°F/°C)
50 / 10
50 / 10
50 / 10
50 / 10
50 / 10
50 / 10
Max water Temperature – Space
Heating (°F/°C)
194 / 90
194 / 90
194 / 90
194 / 90
194 / 90
194 / 90
Max equivalent vent length 3"
(each side)
120'
120'
120'
120'
120'
120'
Max equivalent vent length 2"
(each side)
35'
35'
35'
35'
35'
35'
* Natural Gas boilers require a Propane conversion kit (see page #3-2, Table 9) to be ordered separately if converting a Natural Gas boiler to Propane. Propane (LP)
boilers require a Natural Gas conversion kit (see page #3-2, Table 9) to be ordered separately if converting a Propane boiler to Natural Gas.
† boilers are shipped with 30 psig pressure relief valve
SPECIFICATIONS