STANDARD LEDs

LED

ACTUATOR STATUS

1

GREEN ON

The actuator arrived at the extreme point of the stroke read

2

GREEN BLINKING

The actuator arrived at the intermediate point of the stroke read

3

RED GREEN BLINKING The actuator is reading the stroke or it is going to initial position

4

RED GREEN ON

Manual control ON, the actuators ignores the control signal. 

ATTENTION! The electronic board is electrically supplied

DIMENSIONS [mm]

234

194

86

122

177

194

122

sales@ibc.ie (ROI/INTL.)

 

bill@ibc.ie

 (NI/UK)

DISTRIBUTION PARTNER:

Summary of Contents for MVE2 Series

Page 1: ...and it is able to self calibrate on a different stroke without the need of any user action this function is DIP switch selectable on the field MVE2xx has intelligent behaviour and alarm functionality...

Page 2: ...ion until it is raised again then board and motor will be powered again At the end of this operation the actuator moves to initial position on the basis of DIP n 1 setting then it follows the control...

Page 3: ...ng accordingly see Diagnostic Alarm Function Table ASSEMBLING The actuator can be mounted with any orientation but never up side down When the fluid temperature exceed 120 C the actuator shall be moun...

Page 4: ...o H2 X S and H3 X S with AG82 with AG82 Siemens with AG70 10 with AG70 14 Danfoss VR VF S models with AG60 07 TAC DN15 V298 with AG60 08 TAC DN15 V2XX V3XX with AG60 09 Honeywell with AG60 10 Airtek w...

Page 5: ...m Y2 Close V 16 V DC Voltage Output max 25 mA AWG20 min 0 5mm2 max 1 5mm2 200 m M 0 V Common U 2 10 V DC Feedback Output Signal AWG20 min 0 5mm2 max 1 5mm2 200 m M 0 V Common Note To avoid damages to...

Page 6: ...3 Selection of sequence mode control range defined by DIP n 5 4 Modulating Control 0 10 V DC DIP n 2 OFF only Modulating Control 2 10 V DC DIP n 2 OFF only 5 Sequence Control 0 5 V DC with DIP n 4 OF...

Page 7: ...st the new stroke limit then it goes back to the initial position still signalling the anomaly until it is not within 60mm The actua tor does not calibrate the stroke after 10s wrong range Valve with...

Page 8: ...me point of the stroke read 2 GREEN BLINKING The actuator arrived at the intermediate point of the stroke read 3 RED GREEN BLINKING The actuator is reading the stroke or it is going to initial positio...

Reviews: