1-19
INSTALLATION
SFC BOILER / WATER HEATERS - SFC 199
Figure 18: Condensate trap drainage
Figure 19: Condensate neutralization tank
WARNING
If discharging condensates into
building drain piping materials
that are subject to corrosion,
you must use a neutralization
package.
CAUTION
When a condensate
neutralization package
is installed, the pH of the
condensate discharge must
be measured on a regular
schedule to ensure the
neutralizing agent is active
and effective.
DANGER
The water in the condensate
neutralizer can cause severe
burns to the skin. Use extreme
caution when servicing the
condensate neutralizer. Wear
protective gloves and eyewear.