3.4 FUEL CONVERSION
The SFC series modulating unit is factory fire-tested to operate with natural gas.
The rating plate is marked to indicate which fuel the particular unit has been set
up with. Firing a unit with a fuel other than what is listed on the rating plate is
prohibited unless the following conversion procedure is completed by a qualified
technician.
Fuel conversion requires hardware adjustments (orifice replacement) as well as
measurement and possible tuning of the low fire mixture. Detailed instructions
including parts and labeling are found in Fuel Conversion kits.
Refer to Table 11
for the correct kit number.
NATURAL GAS
PROPANE
CO
2
VALUE (%) AT HIGH FIRE WITH THE FRONT COVER OPEN
Max. CO
2
value
10.1%
11.5%
Min. CO
2
value
9.1%
9.8%
CO
2
VALUE (%) AT LOW FIRE WITH THE FRONT COVER OPEN
Max. CO
2
value
= Actual value at High fire
= Actual value at High fire
– 0.3%
Min. CO
2
value
9.1%
9.5%
Table 12: CO
2
Values and High and Low Fire
The following procedure must be carried out by a qualified technician.
1.
Ensure that the gas supply is turned off at the manual gas valve.
2.
Disconnect the electrical power.
3.
Disconnect the nut at the gas valve outlet (top of the gas valve) and remove
the orifice and O-ring.
4.
Insert the correct orifice into the O-ring, and re-install into the nut at the gas
valve outlet (top of the gas valve) and then tighten the nut.
5.
Restore the gas supply by opening the manual gas valve.
6.
Test for leaks by using an approved leak detection solution on all joints.
7.
Carefully follow the
“Prior to Start-Up” – Section 3.2 and “Commissioning” –
Section 3.3 procedures on the preceeding pages 3-2 and 3-3.
DANGER
Operating any IBC unit using
a fuel other than the fuel
listed on its rating plate is
prohibited. If the information
in this section related to
conversion to alternative
fuels is not followed exactly,
a dangerous situation can
result, leading to fire or
explosion, which may cause
property damage, personal
injury, or loss of life.
Figure 42: Orifice and O-ring
PROPANE ORIFICE CHART
MODEL
NUMBER
ORIFICE
SIZE
SFC 199
535
NATURAL GAS ORIFICE
CHART
MODEL
NUMBER
ORIFICE
SIZE
SFC 199
660
ALTERNATIVE
NATURAL GAS ORIFICES
FOR CALORIFIC VALUES
750–900 BTU/FT
3
MODEL
NUMBER
ORIFICE
SIZE
SFC 199
725