Combustion Test Target Ranges

 

Figure 1 Gas valve and fan

The Low Fire (Zero-offset) valve adjustment 

cap on the gas valve has been factory set. 

Do not tamper with or adjust this screw in the 

field. Contact the factory for written 

instructions if considering field adjustment of 

the Low Fire (zero offset) adjustment.

The High Fire (Gas:Air) ratio adjustment 

screw is a slotted brass screw to the left of 

the long brass protrusion on the front of the 

gas valve. It will have to be adjusted to attain 

optimum combustion results whenever fuel 

conversion is undertaken; however, no 

mixture adjustment must be performed 

unless done by a qualified technician using 

properly functioning and calibrated 

combustion analyzing equipment.

Fuel

High Fire

Low Fire

Co Max PPM

 

Range

Target

Range

Target

 

Natural Gas 

9.0 – 10.0

9.5

8.2 – 9.2

8.7

< 150

Propane 

10.3 – 11.3

10.8

9.3 – 10.3

9.8

< 250

Table 1 

 Combustion test target ranges - CO

2

 / Maximum CO

Note

: Low Fire CO2 should be at least 0.5% lower than High Fire CO2.