Flue gas exhaust: condensate and rain water, flow back from the venting system.
Warning
- Risk of damage to appliance. Ensure that rain water is prevented from entering
air intake piping.
Condensate water line
Warning
- Risk of damage to appliance. All condensate discharge lines, including
neutralization tank inlet, must be at a lower elevation than the condensate water line of the
appliance.
Affix hose to drainage piping
Factory-supplied condensate trap
Confirm slope. Condensate hose and drain piping to slope toward drain and be secured to
prevent accidental disassembly.
Drain materials subject to corrosion must be protected by acid neutralization,
To drain.
Figure 29
Condensate trap drainage
Free flow of condensate from venting systems and pressure vessel must be maintained at
all times. Trap and condensate drain piping must be accessible to allow regular inspection
and cleaning.
40
Section: Installation