7.2.1 Touchscreen boiler controller
Maintenance Required for Boiler Controller
Frequency
Check
Check that boiler operation is consistent with the steps in the
Touchscreen Boiler Controller Manual.
Annually
□
Check that water temperature targets and setpoint is satisfactory and
have not been adversely amended.
Annually
□
Check the operating history using the boiler's Logs menu and Error
Logs menu.
The controller tracks the duty cycle of the boiler in each of the loads
separately. This information can be used to adjust the water
temperatures of each load.
Annually
□
Caution
The owner is responsible for general care of the boiler. Improper maintenance of the
boiler may result in a hazardous condition.
7.2.2 General boiler maintenance
Boiler
Component
Maintenance Required
Frequency
Check
Condensate
trap
Remove and clean annually (see
). Ensure that the trap has
been re-filled completely before firing the boiler.
Annually
□
If condensate neutralization is used, check the pH level
of condensate discharge.
Annually
□
Burner
Warning
When removing the burner for inspection or
boiler servicing, examine the sealing gaskets
and replace if damaged. Upon re-assembly,
test all sealing areas to ensure there is no
leakage of combustible gas/air premix.
Remove the burner to inspect for extent of fouling (see
Replacing the burner on page 85
.
a. Wash the burner from outside with a domestic
water pressure, and dry using compressed air.
b. Evaluate the magnitude of clearing required, and
As needed
□
74
Section: Service and maintenance
Summary of Contents for SL Series
Page 8: ...Intentionally left empty...
Page 12: ...Figure 5 Top view SL 40 399 G3 Figure 6 Bottom view SL 40 399 G3 8 Section Specifications...
Page 14: ...Intentionally left empty...
Page 64: ...Figure 40 Electric wiring connections 60 Section Installation...
Page 76: ...Intentionally left empty...
Page 96: ...Intentionally left empty...
Page 108: ...Intentionally left empty...
Page 110: ...Internal wiring diagram Figure 46 Internal wiring diagram 106 Section Appendices...
Page 111: ...Sequence of operations Figure 47 Sequence of Operation 107 Sequence of operations...