background image

9

USER’S INFORMATION MANUAL

SL SERIES BOILERS

MAINTENANCE

Daily Maintenance 

  Check the surrounding area – inspect for water leaks in the general area 

around the boiler and boiler piping

  Check the system pressure. The heating system pressure should not exceed 

25psi (SL 80-399 - 75psi) and not drop below 10psi in most applications. If the 

pressure is outside this normal range or if the water pressure fluctuates more 

than 2-3psi, contact your qualified service technician for service.

  Check the area around the boiler and the air intake opening for obstructions 

and chemical contaminates.

Monthly Maintenance 

  Check all the Daily Maintenance items.

  Check the pressure relief valve and discharge piping for signs of leakage 

or moisture. If water or moisture is found, contact your qualified service 

technician as soon as possible for service.

  Check the condensate trap and outlet pipe. The condensate trap shall be full 

of water. The outlet hose may be connected to a condensate neutralizer, if so, 

check the pH of the water coming out of the neutralizer is above 6.0pH. If the 

pH is below 6.0 then the neutralizer will need to be re-charged or replaced. 

Contact your qualified service technician for service.

  Inspect the flue gas exhaust and air intake connections. All connections 

should be tight and leak free.

  Inspect flue gas exhaust piping, combustion air piping and terminations.

Annual Maintenance

The boiler must be inspected by your qualified service technician for the following:

  Check the Error Logs for any issues.

  Inspect the flue gas exhaust and air intake connections. All connections 

should be tight and leak free.

  Inspect flue gas exhaust piping, combustion air piping and terminations.

  Inspect the boilers interior and vacuum if required.

  Check for water, gas and condensate leaks in the boiler and around the boiler.

  Check the condensate trap and clean if required. Re-fill the trap and re-install 

the trap hook.

  Check the water pressure, expansion tank and pumps.

  Check the electrical connections.

  Check the ignition electrode and remove oxidation from the electrode. 

Replace if necessary.

  Check the gas valve and ignition cable.

  Check the controller settings.

  Check the burners flame. Should be a quick and quiet ignition across the full 

burner.

  If required, clean the heat exchanger and the burner.

WARNING

Annual Maintenance must only 

be done by a qualified service 

technician.

CAUTION

The heat exchanger has a small 

amount of combustion chamber 

insulation (refractory), which 

contains ceramic fibers. When 

exposed to extremely high 

temperatures, the ceramic fibers, 

which contain crystalline silica, 

can be converted into cristobalite 

- which is classified as a possible 

human carcinogen.
Care should be taken to avoid 

disturbing or damaging the 

refractory. If damage occurs, 

contact the factory for directions. 

Avoid breathing and contact with 

skin and eyes and follow these 

precautions:

1. 

For conditions of frequent  

use or heavy exposure, 

respirator protection is 

required. Refer to the “NIOSH 

Guide to the Selection and 

Use of Particulate Respirators 

Certified under 42 CFR 

84” for selection and use 

of respirators certified by 

NIOSH. For the most current 

information, NIOSH can be 

contacted at 1-800-356-4676 

or on the web at www.cdc.

gov/niosh.

2. 

Wear long sleeved, loose 

fitting clothing, gloves and 

eyes protection.

3. 

Assure adequate ventilation.

4. 

Wash with soap and water 

after contact.

5. 

Wash potentially 

contaminated clothes 

separately from other 

laundry and rinse washing 

machine thoroughly.

6. 

Discard used insulation in an 

air tight plastic bag.

NIOSH stated first aid:

• 

Eye contact - Irrigate and 

wash immediately.

• 

Breathing - Provide fresh air.

Summary of Contents for SL SERIES

Page 1: ...pliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a nearby phone Fo...

Page 2: ...information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life WARNING Points out a potentially hazardous situation which mu...

Page 3: ...3 USER S INFORMATION MANUAL SL SERIES BOILERS WARNINGS 3 IBC BOILER CONTROLLER 6 LIGHTING AND SHUTTING DOWN THE BOILER 8 MAINTENANCE 9 SERVICE RECORD 11 CONTENTS...

Page 4: ...llows Acidity pH is to be between 6 5 and 8 5 Chloride is to be less than 125 mg l Iron is to be less than 0 3 mg l Cu less than 0 1 mg l Conductivity is to be less than 400 S cm at 25 C Hardness is t...

Page 5: ...tible materials gasoline and other flammable vapours and liquids WARNING Combustion air must not be drawn from areas containing corrosive air from swimming pools or spas including air directly next to...

Page 6: ...e Home Screen Internet LAN connectivity BACnet with activation Control When the boiler is first energized the controller will go through a power up sequence that will take approximately 90 seconds Dur...

Page 7: ...play will be showing the Home screen that includes details of the current boiler status If the controller has been left on the Home screen long enough user adjustable 10 minutes by default the display...

Page 8: ...USER S INFORMATION MANUAL 8 SL SERIES BOILERS LIGHTING AND SHUTTING DOWN THE BOILER clockwise open close...

Page 9: ...r and vacuum if required Check for water gas and condensate leaks in the boiler and around the boiler Check the condensate trap and clean if required Re fill the trap and re install the trap hook Chec...

Page 10: ...chemicals or glycol solutions If the system employs plain water the boiler auto fill valve must be turned on in order to recharge the lost fluid Blocked Vent Safety System The boiler is equipped with...

Page 11: ...11 USER S INFORMATION MANUAL SL SERIES BOILERS SERVICE RECORD DATE LICENSED CONTRACTOR DESCRIPTION OF WORK DONE...

Page 12: ...USER S INFORMATION MANUAL 12 SL SERIES BOILERS NOTES...

Page 13: ...13 USER S INFORMATION MANUAL SL SERIES BOILERS NOTES...

Page 14: ...E MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE An external energy management system is installed that reduces the boiler water temperature as the heating load decreases Thi...

Page 15: ...REVISION HISTORY R1 JULY 2014 Initial release R2 MAY 2015 Address update...

Page 16: ...IBC Technologies Inc 8015 North Fraser Way Burnaby BC Canada V5J 5M8 Tel 604 877 0277 Fax 604 877 0295 www ibcboiler com 120 203 A R2 May 2015 IBC Technologies Inc 2015...

Reviews: