8.1.4.1 Table showing LED operating status
Its two status LEDs indicate the operating status as shown in the table below.
SIM Status Indicators
LED 1
LED 2
State
Description, LED status
indication
Rapid flash
Rapid flash
Power up or
resetting
Startup checks and initialization
Off
Off
Standby
LED 1 Off = No flame or sparking
LED 2 = Burner-on call state
Off
On
Pre-purge or
inter-purge
LED 1 Off = No flame or sparking
LED 2 = Burner-on call state
On
On
Heating
LED 1 On = Flame detected
LED 2 = Burner-on call State
Rapid flash
On
Igniting
LED 1 Flashing - Electrode sparking
LED 2 = Burner-on call state
Off
Flashing
Lockout
Possible errors:
An operating limit was
exceeded
A sequence failed
An external sensor fault was
detected.
Flash alternately
with LED 2
Flash alternately
with LED 1
Fail-safe
An error was detected - the boiler
requires a power cycle
Table 14
SIM+ LED status Indicators
8.2 Troubleshooting error messages
Warning
Never attempt to repair the control module (circuit board). If the control module is
defective, replace it immediately.
Errors shown on the touchscreen controller are described below as well as diagnoses and fixes.
96
Section: Troubleshooting
Summary of Contents for SL Series
Page 8: ...Intentionally left empty...
Page 12: ...Figure 5 Top view SL 40 399 G3 Figure 6 Bottom view SL 40 399 G3 8 Section Specifications...
Page 14: ...Intentionally left empty...
Page 64: ...Figure 40 Electric wiring connections 60 Section Installation...
Page 76: ...Intentionally left empty...
Page 96: ...Intentionally left empty...
Page 108: ...Intentionally left empty...
Page 110: ...Internal wiring diagram Figure 46 Internal wiring diagram 106 Section Appendices...
Page 111: ...Sequence of operations Figure 47 Sequence of Operation 107 Sequence of operations...