The controller provides overall management of the boiler operations including:
Power-up, self-diagnostics, easy Load parameter adjustments
Burner operation, safety management systems, call-for-heat
management and load priority
Real time boiler data
Temperature and throttle operation
Maintenance of operational and error service logs
2-way communication between other IBC boilers and controls
Internet connection and communication
Operational and historical data may be accessed from the
Status
menu >
Load Status
>
Load Profiles
and
Load Statistics
screens. Also
in the
Status
menu, you can view error logs, including records of all
errors since original power-up complete with the date and time of the error.
4.2 Control interface
The control interface is provided through a color touchscreen display. The touchscreen responds
to a light finger touch on the screen. You can also use a stylus, pencil, or similar device to operate
the touch controls. Do not use a sharp or metallic object such as a screw driver as it could damage
the touchscreen.
Prior to any interaction with the touchscreen, the display shows the Home screen details of the
current boiler status. If the controller has been left on, the Home screen long enough (user
adjustable, 10 minutes by default) the display dims to save power.
The control automatically returns to the home screen if left unattended. The screens will step back
one screen at a time in 10-minute increments if the touchscreen has not been touched. The pop-
up windows will also step back automatically in 2-minute intervals.
The boiler status bar indicates if the boiler is in a normal, warning or alarm state. When no warning
or alarm state is present, the bar will be green and the time will be displayed inside the green area.
The bar can also be yellow or red corresponding a warning or alarm state. Text inside the bar will
indicate the specific warning or alarm present. If more than one alarm is present the text display
will rotate though the alarms that are present.
62
Section: About the boiler controller
Summary of Contents for SL Series
Page 8: ...Intentionally left empty...
Page 12: ...Figure 5 Top view SL 40 399 G3 Figure 6 Bottom view SL 40 399 G3 8 Section Specifications...
Page 14: ...Intentionally left empty...
Page 64: ...Figure 40 Electric wiring connections 60 Section Installation...
Page 76: ...Intentionally left empty...
Page 96: ...Intentionally left empty...
Page 108: ...Intentionally left empty...
Page 110: ...Internal wiring diagram Figure 46 Internal wiring diagram 106 Section Appendices...
Page 111: ...Sequence of operations Figure 47 Sequence of Operation 107 Sequence of operations...