Releasing the ruggedized brace
You might need to release the ruggedized brace. Use the procedure in this section to perform this task.
To access the back of a system that is installed in a rack with a ruggedized kit, complete the following
steps to release the ruggedized brace:
1.
Remove the brace thumbscrew
(8)
.
2.
Swing the brace
(10)
out of the rack.
3.
Access the system and reinstall the brace.
Releasing the side panel with a ruggedized kit
You might need to release the side panel on the rack. Use this procedure to perform this task.
The ruggedized kit contains securing screws that secure the side panels to the rack. To remove a securing
screw, complete the following steps:
1.
If necessary, open or remove the back rack door.
2.
Locate the securing screw mount
(11)
for the side door that will be removed.
Figure 115. Releasing the brace to access systems
114
Installing into a rack