To set the power strategy, complete the following steps:
1. Make sure that the UPS is in Standby mode.
2. From the main menu, press the down (
) button to scroll to the
Configuration
menu, and press the
OK
button.
3. Press the down (
) button to scroll to
Power Strategy
, and press the
OK
button.
4. Press the down (
) button to select the power strategy that you want to set
and press the
OK
button.
5. Press the
OK
button for 1 second to confirm.
Note:
The UPS tests the bypass source for 5 consecutive minutes of stable power
before it transfers to High Efficiency mode.
Retrieving the alarm history
To retrieve the alarm history through the display, complete the following steps:
1. From the main menu, press the down (
) button to scroll to the
Alarm history
menu, and press the OK button.
2. Press the down (
) button to scroll through the listed events, notices, and
alarms.
3. Press the escape (X) button to return to the previous menu.
Behavior on overload
The following table explains how the UPS responds to an overload condition.
Table 10. Behavior on overload
Overload
severity
Load level
On utility power
On Bypass / High
Efficiency
On Battery / Converter
Level 1
100% to
101%
Overload alarm only and
support load indefinitely
Overload alarm only and
support load indefinitely
Overload alarm only,
support load until low
battery shutdown level is
reached
Level 2
102% to
110%
Transfer to Bypass after 12
seconds (±1 sec)
If Bypass is not available,
transfer to Fault mode
after 12 seconds (±1 sec)
Transfer to Fault mode in
2 minutes (± 1 sec)
Transfer to Fault mode
after 12 seconds (±1 sec)
or until low battery
shutdown level is reached
Level 3
> 110%
Transfer to Bypass
immediately
If Bypass is not available,
transfer to Fault mode in
300 ms to 1 sec
Transfer to Fault mode in
300 ms to 1 sec
Transfer to Fault mode in
300 ms to 1 sec
Chapter 3. Operating the uninterruptible power supply
37
Summary of Contents for 11000 VA LCD 5U
Page 2: ......
Page 13: ...Taiwan Class A compliance statement 71 Index 73 Contents xi...
Page 14: ...xii 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 40: ...26 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 56: ...42 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 60: ...46 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 76: ...62 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 86: ...72 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 90: ...76 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 91: ......
Page 92: ...Part Number 60Y1454 Printed in USA 1P P N 60Y1454...