2. Remove the four screws that secure the terminal block cover to the UPS. Save
the screws.
Input terminal
block cover
3. Punch a hole in the terminal block cover for the input conduit, using a round
knockout punch or similar device. The hole must accommodate a 19 - 25.4 mm
(0.75 - 1 in.) Intermediate Metal Conduit (IMC).
4. Pull the input wire through the conduit, leaving approximately 0.5 m (2 ft) of
exposed wire. Attach a flexible metal fitting to the end of the conduit.
5. Insert the conduit through the wiring access entry and attach the conduit fitting
to the panel. Strip 1.5 cm (0.5 in.) of insulation from the end of each incoming
wire.
6.
CAUTION:
The UPS does not have an automatic protection device against
current backfeed. Install an external isolating device as shown in the following
illustration. Check for hazardous voltage between all terminals before operating
on this circuit.
External distribution panel
Uninterruptible power supply
B
Q
T
N/L2
L/L1
Coil remote switch
Magneto-thermal input main switch
AC contactor rated 208 - 240 V, 68 A; 220 -
240 Vac, 68 A; or 220 - 240 Vac, 80 A
Neutral/L2
L1 Line input
Q
L/L1
N/L2
T
B
L/L1
N/L2
L/L1
N/L2
Chapter 2. Installing the uninterruptible power supply
17
Summary of Contents for 11000 VA LCD 5U
Page 2: ......
Page 13: ...Taiwan Class A compliance statement 71 Index 73 Contents xi...
Page 14: ...xii 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 40: ...26 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 56: ...42 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 60: ...46 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 76: ...62 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 86: ...72 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 90: ...76 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 91: ......
Page 92: ...Part Number 60Y1454 Printed in USA 1P P N 60Y1454...