To set the restart delay times for each load segment, complete the following steps:
1. From the main menu, press the down (
) button to scroll to the
Configuration
menu, and press the OK button.
2. Press the down (
) button to scroll to
Automatic Start Delay
, and press the
OK button.
3. Press the down (
) button to select the load segment that you want to set and
press the OK button.
4. Press the down (
) button to select the restart delay for the load segment.
You can specify one of the following options for the restart delay time for each
load segment:
v
Select zero seconds to restart immediately.
v
Select 1 - 32767 seconds to delay for the specified time.
v
Select Off.
5. Press the OK button for 1 second to confirm.
6. Repeat step 3 to step 5 to set the other load segment, if applicable.
Notes:
1. Load segment on/off commands that are issued through the
Control
menu
override the user settings for load segments.
2. A single load segment delay applies to both receptacles. However, there is an
additional automatic 1-second delay between closing segments 1 and 2. The
delay is always present when an On command is issued for both segments at
the same time.
Configuring automatic on battery shutdown
You can use the
Automatic on Battery Shutdown
setting to configure how soon
the load segment shuts down when the uninterruptible power supply transfers to
Battery mode:
v
If the
Automatic on Battery Shutdown
setting is set to Off (default), the load
segment turns off only when you manually press the button, issue an external
command, or turn it off through the display (
Control > Load Segments
).
v
If the
Automatic on Battery Shutdown
setting is set to zero seconds (0s), the
load segment turns off automatically when the uninterruptible power supply on
Battery state is activated.
v
If you select a value, the load segment turns off automatically after the selected
delay while the uninterruptible power supply operates on battery, but the
shutdown is canceled if the utility power returns before the delay has expired.
To set the shutdown times for each load segment, complete the following steps:
1. From the main menu, press the down (
) button to scroll to the
Configuration
menu, and press the OK button.
2. Press the down (
) button to scroll to
Automatic on Battery Shutdown
, and
press the OK button.
3. Press the down (
) button to select the load segment that you want to set and
press the OK button.
4. Press the down (
) button to select the shutdown delay for the load segment.
5. Press the OK button for 1 second to confirm.
6. Repeat step 3 to step 5 to set the other load segment, if applicable.
Chapter 3. Operating the uninterruptible power supply
27
Summary of Contents for 1500VA
Page 1: ...1000 VA LCD Tower UPS and 1500 VA LCD Tower UPS Installation and Maintenance Guide ...
Page 2: ......
Page 3: ...1000 VA LCD Tower UPS and 1500 VA LCD Tower UPS Installation and Maintenance Guide ...
Page 50: ...40 1000 VA and 1500 VA LCD Tower UPS Installation and Maintenance Guide ...
Page 67: ......
Page 68: ... Part Number 60Y1421 Printed in USA 1P P N 60Y1421 ...