3. The pins must be open to keep the UPS running. If the UPS shuts down
because the remote emergency power-off connector pins are shorted, restart
the UPS by reopening the remote emergency power-off connector pins and
turning on the UPS manually. Maximum resistance in the shorted loop is 10
ohm.
4. To avoid accidental load loss, always test the remote emergency power-off
function before you apply your critical load.
To connect a remote emergency power-off switch, complete the following steps:
1. Turn off the UPS, disconnect all external cables, and make sure that the UPS is
disconnected from utility power.
2. Remove the remote emergency power-off connector from the accessory kit.
Note:
Make sure that no jumper is installed in the remote emergency power-off
connector. If a jumper is installed, remove it before you connect to the remote
emergency power-off connector.
12
6000 VA UPS and 6000 VA EBM: Installation and Maintenance Guide