2. Remove the four screws that secure the terminal block cover to the UPS. Save
the screws.
3. Punch a hole in the terminal block cover for the input conduit, using a round
knockout punch or similar device. The hole must accommodate a 20 - 25.5 mm
(0.75 - 1 in.) Intermediate Metal Conduit (IMC).
4. Pull the input wire through the conduit, leaving approximately 0.5 m (2 ft) of
exposed wire. Attach a flexible metal fitting to the end of the conduit.
5. Insert the conduit through the wiring access entry and attach the conduit fitting
to the panel. Strip 1.5 cm (0.5 in.) of insulation from the end of each incoming
wire.
Chapter 2. Installing the uninterruptible power supply
15