Table 8. Configuration settings (continued)
Description
Available settings
Default setting
LCD contrast
[-5], [-4], [-3], [-2], [-1], [+0], [+1], [+2], [+3], [+4], [+5]
The display contrast is adjustable from -5 to +5. This range
covers the maximum adjustment for contrasting the background
with the text in the visual display of the control panel.
[+0]
REPO input polarity
[Open] [Closed]
If Open, the normally-open contacts activate the alarm when the
contacts close. If Closed, the normally-closed contacts activate
the alarm when the contacts open.
Open
Transferring the UPS between modes
Transferring between modes includes:
v
Transferring from Normal to Bypass mode
v
Transferring from Bypass to Normal mode
Transferring from Normal to Bypass Mode
To transfer from Normal to Bypass mode, complete the following steps:
1. From the main menu, press the down (
) button to scroll to the Control menu,
and press the OK button.
2. Press the down (
) button to scroll to Go to Bypass, and press the OK button.
The text on the screen changes to Manual Bypass Command Sent.
Transferring from Bypass to Normal Mode
To transfer from Bypass to Normal mode, complete the following steps:
1. From the main menu, press the down (
) button to scroll to the Control menu,
and press the OK button.
2. Press the down (
) button to scroll to Go to Normal, and press the OK button.
The text on the screen changes to Normal Mode Command Sent.
Retrieving the alarm history
To retrieve the alarm history through the display, complete the following steps:
1. From the main menu, press the down (
) button to scroll to the
Alarm History
menu, and press the OK button.
2. Press the down (
) button to scroll through the listed events, notices, and
alarms.
3. Press the escape (X) button to return to the previous menu.
26
6000 VA UPS and 6000 VA EBM: Installation and Maintenance Guide
Summary of Contents for 6000 VA LCD 4U
Page 2: ......
Page 14: ...xii 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Page 32: ...18 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Page 60: ...46 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Page 70: ...56 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Page 74: ...60 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Page 82: ...68 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Page 86: ...72 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Page 87: ......
Page 88: ...Part Number 81Y1032 Printed in USA 1P P N 81Y1032...